Vulnerabilities (CVE)

Join the Common Vulnerabilities and Exposures (CVE) community and start to get notified about new vulnerabilities.

Filtered by vendor Rockwellautomation Subscribe
Total 192 CVE
CVE Vendors Products Updated CVSS v2 CVSS v3
CVE-2018-17924 1 Rockwellautomation 32 1756-en2f Series A, 1756-en2f Series A Firmware, 1756-en2f Series B and 29 more 2022-05-02 7.8 HIGH 8.6 HIGH
Rockwell Automation MicroLogix 1400 Controllers and 1756 ControlLogix Communications Modules An unauthenticated, remote threat actor could send a CIP connection request to an affected device, and upon successful connection, send a new IP configuration to the affected device even if the controller in the system is set to Hard RUN mode. When the affected device accepts this new IP configuration, a loss of communication occurs between the device and the rest of the system as the system traffic is still attempting to communicate with the device via the overwritten IP address.
CVE-2020-12028 1 Rockwellautomation 1 Factorytalk View 2022-04-25 5.5 MEDIUM 8.1 HIGH
In all versions of FactoryTalk View SEA remote, an authenticated attacker may be able to utilize certain handlers to interact with the data on the remote endpoint since those handlers do not enforce appropriate permissions. Rockwell Automation recommends enabling built in security features found within FactoryTalk View SE. Users should follow guidance found in knowledge base articles 109056 and 1126943 to set up IPSec and/or HTTPs.
CVE-2021-22681 1 Rockwellautomation 20 Compact Guardlogix 5370, Compact Guardlogix 5380, Compactlogix 1768 and 17 more 2022-04-25 7.5 HIGH 9.8 CRITICAL
Rockwell Automation Studio 5000 Logix Designer Versions 21 and later, and RSLogix 5000 Versions 16 through 20 use a key to verify Logix controllers are communicating with Rockwell Automation CompactLogix 1768, 1769, 5370, 5380, 5480: ControlLogix 5550, 5560, 5570, 5580; DriveLogix 5560, 5730, 1794-L34; Compact GuardLogix 5370, 5380; GuardLogix 5570, 5580; SoftLogix 5800. Rockwell Automation Studio 5000 Logix Designer Versions 21 and later and RSLogix 5000: Versions 16 through 20 are vulnerable because an unauthenticated attacker could bypass this verification mechanism and authenticate with Rockwell Automation CompactLogix 1768, 1769, 5370, 5380, 5480: ControlLogix 5550, 5560, 5570, 5580; DriveLogix 5560, 5730, 1794-L34; Compact GuardLogix 5370, 5380; GuardLogix 5570, 5580; SoftLogix 5800.
CVE-2017-14469 1 Rockwellautomation 2 Micrologix 1400, Micrologix 1400 B Firmware 2022-04-19 7.5 HIGH 9.8 CRITICAL
An exploitable access control vulnerability exists in the data, program, and function file permissions functionality of Allen Bradley Micrologix 1400 Series B FRN 21.2 and before. A specially crafted packet can cause a read or write operation resulting in disclosure of sensitive information, modification of settings, or modification of ladder logic. An attacker can send unauthenticated packets to trigger this vulnerability. Required Keyswitch State: REMOTE or PROG Associated Fault Code: 0028 Fault Type: Non-User Description: Values 0x01 and 0x02 are invalid values for the user fault routine. By writing directly to the file it is possible to set these values. When this is done and the device is moved into a run state, a fault is triggered. NOTE: This is not possible through RSLogix.
CVE-2017-14470 1 Rockwellautomation 2 Micrologix 1400, Micrologix 1400 B Firmware 2022-04-19 7.5 HIGH 9.8 CRITICAL
An exploitable access control vulnerability exists in the data, program, and function file permissions functionality of Allen Bradley Micrologix 1400 Series B FRN 21.2 and before. A specially crafted packet can cause a read or write operation resulting in disclosure of sensitive information, modification of settings, or modification of ladder logic. An attacker can send unauthenticated packets to trigger this vulnerability. Required Keyswitch State: REMOTE or PROG or RUN Description: The value 0xffffffff is considered NaN for the Float data type. When a float is set to this value and used in the PLC, a fault is triggered. NOTE: This is not possible through RSLogix.
CVE-2017-14471 1 Rockwellautomation 2 Micrologix 1400, Micrologix 1400 B Firmware 2022-04-19 7.5 HIGH 9.8 CRITICAL
An exploitable access control vulnerability exists in the data, program, and function file permissions functionality of Allen Bradley Micrologix 1400 Series B FRN 21.2 and before. A specially crafted packet can cause a read or write operation resulting in disclosure of sensitive information, modification of settings, or modification of ladder logic. An attacker can send unauthenticated packets to trigger this vulnerability. Required Keyswitch State: REMOTE or PROG Associated Fault Codes: 0023, 002e, and 0037 Fault Type: Recoverable Description: The STI, EII, and HSC function files contain bits signifying whether or not a fault has occurred. Additionally there is a bit signaling the module to auto start. When these bits are set for any of the three modules and the device is moved into a run state, a fault is triggered.
CVE-2017-14472 1 Rockwellautomation 2 Micrologix 1400, Micrologix 1400 B Firmware 2022-04-19 7.5 HIGH 9.8 CRITICAL
An exploitable access control vulnerability exists in the data, program, and function file permissions functionality of Allen Bradley Micrologix 1400 Series B FRN 21.2 and before. A specially crafted packet can cause a read or write operation resulting in disclosure of sensitive information, modification of settings, or modification of ladder logic. An attacker can send unauthenticated packets to trigger this vulnerability. Required Keyswitch State: Any Description: Requests a specific set of bytes from an undocumented data file and returns the ASCII version of the master password.
CVE-2017-12090 1 Rockwellautomation 2 Micrologix 1400, Micrologix 1400 B Firmware 2022-04-19 7.8 HIGH 7.5 HIGH
An exploitable denial of service vulnerability exists in the processing of snmp-set commands of the Allen Bradley Micrologix 1400 Series B FRN 21.2 and below. A specially crafted snmp-set request, when sent without associated firmware flashing snmp-set commands, can cause a device power cycle resulting in downtime for the device. An attacker can send one packet to trigger this vulnerability.
CVE-2017-14473 1 Rockwellautomation 2 Micrologix 1400, Micrologix 1400 B Firmware 2022-04-19 7.5 HIGH 9.8 CRITICAL
An exploitable access control vulnerability exists in the data, program, and function file permissions functionality of Allen Bradley Micrologix 1400 Series B FRN 21.2 and before. A specially crafted packet can cause a read or write operation resulting in disclosure of sensitive information, modification of settings, or modification of ladder logic. An attacker can send unauthenticated packets to trigger this vulnerability. Required Keyswitch State: Any Description: Reads the encoded ladder logic from its data file and print it out in HEX.
CVE-2017-12089 1 Rockwellautomation 2 Micrologix 1400, Micrologix 1400 B Firmware 2022-04-19 7.8 HIGH 7.5 HIGH
An exploitable denial of service vulnerability exists in the program download functionality of Allen Bradley Micrologix 1400 Series B FRN 21.2 and before. A specially crafted packet can cause a device fault resulting in halted operations. An attacker can send an unauthenticated packet to trigger this vulnerability.
CVE-2017-12088 1 Rockwellautomation 2 Micrologix 1400, Micrologix 1400 B Firmware 2022-04-19 7.8 HIGH 7.5 HIGH
An exploitable denial of service vulnerability exists in the Ethernet functionality of the Allen Bradley Micrologix 1400 Series B FRN 21.2 and below. A specially crafted packet can cause a device power cycle resulting in a fault state and deletion of ladder logic. An attacker can send one unauthenticated packet to trigger this vulnerability
CVE-2017-12092 1 Rockwellautomation 2 Micrologix 1400, Micrologix 1400 B Firmware 2022-04-19 5.0 MEDIUM 7.5 HIGH
An exploitable file write vulnerability exists in the memory module functionality of Allen Bradley Micrologix 1400 Series B FRN 21.2 and before. A specially crafted packet can cause a file write resulting in a new program being written to the memory module. An attacker can send an unauthenticated packet to trigger this vulnerability.
CVE-2022-1161 1 Rockwellautomation 48 Compact Guardlogix 5370, Compact Guardlogix 5370 Firmware, Compact Guardlogix 5380 and 45 more 2022-04-18 7.5 HIGH 9.8 CRITICAL
An attacker with the ability to modify a user program may change user program code on some ControlLogix, CompactLogix, and GuardLogix Control systems. Studio 5000 Logix Designer writes user-readable program code to a separate location than the executed compiled code, allowing an attacker to change one and not the other.
CVE-2022-1018 1 Rockwellautomation 3 Connected Components Workbench, Isagraf, Safety Instrumented Systems Workstation 2022-04-12 4.3 MEDIUM 5.5 MEDIUM
When opening a malicious solution file provided by an attacker, the application suffers from an XML external entity vulnerability due to an unsafe call within a dynamic link library file. An attacker could exploit this to pass data from local files to a remote web server, leading to a loss of confidentiality.
CVE-2021-32960 1 Rockwellautomation 1 Factorytalk Services Platform 2022-04-12 6.0 MEDIUM 8.8 HIGH
Rockwell Automation FactoryTalk Services Platform v6.11 and earlier, if FactoryTalk Security is enabled and deployed contains a vulnerability that may allow a remote, authenticated attacker to bypass FactoryTalk Security policies based on the computer name. If successfully exploited, this may allow an attacker to have the same privileges as if they were logged on to the client machine.
CVE-2022-1159 1 Rockwellautomation 10 Compact Guardlogix 5380, Compact Guardlogix 5380 Firmware, Compactlogix 5380 and 7 more 2022-04-08 6.5 MEDIUM 7.2 HIGH
Rockwell Automation Studio 5000 Logix Designer (all versions) are vulnerable when an attacker who achieves administrator access on a workstation running Studio 5000 Logix Designer could inject controller code undetectable to a user.
CVE-2020-25182 3 Rockwellautomation, Schneider-electric, Xylem 31 Aadvance Controller, Isagraf Free Runtime, Isagraf Runtime and 28 more 2022-04-05 4.6 MEDIUM 6.7 MEDIUM
Rockwell Automation ISaGRAF Runtime Versions 4.x and 5.x searches for and loads DLLs as dynamic libraries. Uncontrolled loading of dynamic libraries could allow a local, unauthenticated attacker to execute arbitrary code. This vulnerability only affects ISaGRAF Runtime when running on Microsoft Windows systems.
CVE-2020-25180 3 Rockwellautomation, Schneider-electric, Xylem 31 Aadvance Controller, Isagraf Free Runtime, Isagraf Runtime and 28 more 2022-04-04 4.3 MEDIUM 6.5 MEDIUM
Rockwell Automation ISaGRAF Runtime Versions 4.x and 5.x includes the functionality of setting a password that is required to execute privileged commands. The password value passed to ISaGRAF Runtime is the result of encryption performed with a fixed key value using the tiny encryption algorithm (TEA) on an entered or saved password. A remote, unauthenticated attacker could pass their own encrypted password to the ISaGRAF 5 Runtime, which may result in information disclosure on the device.
CVE-2020-25178 3 Rockwellautomation, Schneider-electric, Xylem 31 Aadvance Controller, Isagraf Free Runtime, Isagraf Runtime and 28 more 2022-04-04 9.3 HIGH 8.8 HIGH
ISaGRAF Workbench communicates with Rockwell Automation ISaGRAF Runtime Versions 4.x and 5.x using TCP/IP. This communication protocol provides various file system operations, as well as the uploading of applications. Data is transferred over this protocol unencrypted, which could allow a remote unauthenticated attacker to upload, read, and delete files.
CVE-2020-25176 3 Rockwellautomation, Schneider-electric, Xylem 31 Aadvance Controller, Isagraf Free Runtime, Isagraf Runtime and 28 more 2022-04-04 9.3 HIGH 9.8 CRITICAL
Some commands used by the Rockwell Automation ISaGRAF Runtime Versions 4.x and 5.x eXchange Layer (IXL) protocol perform various file operations in the file system. Since the parameter pointing to the file name is not checked for reserved characters, it is possible for a remote, unauthenticated attacker to traverse an application’s directory, which could lead to remote code execution.