Vulnerabilities (CVE)

Join the Common Vulnerabilities and Exposures (CVE) community and start to get notified about new vulnerabilities.

Filtered by vendor Rockwellautomation Subscribe
Total 192 CVE
CVE Vendors Products Updated CVSS v2 CVSS v3
CVE-2023-0754 3 Ge, Ptc, Rockwellautomation 9 Digital Industrial Gateway Server, Kepware Server, Kepware Serverex and 6 more 2023-03-03 N/A 9.8 CRITICAL
The affected products are vulnerable to an integer overflow or wraparound, which could allow an attacker to crash the server and remotely execute arbitrary code.
CVE-2023-0755 3 Ge, Ptc, Rockwellautomation 9 Digital Industrial Gateway Server, Kepware Server, Kepware Serverex and 6 more 2023-03-03 N/A 9.8 CRITICAL
The affected products are vulnerable to an improper validation of array index, which could allow an attacker to crash the server and remotely execute arbitrary code.
CVE-2018-19615 1 Rockwellautomation 2 Powermonitor 1000, Powermonitor 1000 Firmware 2023-03-01 4.3 MEDIUM 6.1 MEDIUM
Rockwell Automation Allen-Bradley PowerMonitor 1000 all versions. A remote attacker could inject arbitrary code into a targeted userĂ¢??s web browser to gain access to the affected device.
CVE-2017-12093 1 Rockwellautomation 2 Micrologix 1400, Micrologix 1400 B Firmware 2023-01-27 5.0 MEDIUM 5.3 MEDIUM
An exploitable insufficient resource pool vulnerability exists in the session communication functionality of Allen Bradley Micrologix 1400 Series B Firmware 21.2 and before. A specially crafted stream of packets can cause a flood of the session resource pool resulting in legitimate connections to the PLC being disconnected. An attacker can send unauthenticated packets to trigger this vulnerability.
CVE-2022-3156 1 Rockwellautomation 1 Studio 5000 Logix Emulate 2023-01-06 N/A 7.8 HIGH
A remote code execution vulnerability exists in Rockwell Automation Studio 5000 Logix Emulate software. Users are granted elevated permissions on certain product services when the software is installed. Due to this misconfiguration, a malicious user could potentially achieve remote code execution on the targeted software.
CVE-2022-3752 1 Rockwellautomation 10 Compact Guardlogix 5380, Compact Guardlogix 5380 Firmware, Compactlogix 5380 and 7 more 2022-12-27 N/A 7.5 HIGH
An unauthorized user could use a specially crafted sequence of Ethernet/IP messages, combined with heavy traffic loading to cause a denial-of-service condition in Rockwell Automation Logix controllers resulting in a major non-recoverable fault. If the target device becomes unavailable, a user would have to clear the fault and redownload the user project file to bring the device back online and continue normal operation.
CVE-2022-3166 1 Rockwellautomation 4 Micrologix 1100, Micrologix 1100 Firmware, Micrologix 1400 and 1 more 2022-12-22 N/A 7.5 HIGH
Rockwell Automation was made aware that the webservers of the Micrologix 1100 and 1400 controllers contain a vulnerability that may lead to a denial-of-service condition. The security vulnerability could be exploited by an attacker with network access to the affected systems by sending TCP packets to webserver and closing it abruptly which would cause a denial-of-service condition for the web server application on the device
CVE-2022-3157 1 Rockwellautomation 12 Compact Guardlogix 5370, Compact Guardlogix 5370 Firmware, Compact Guardlogix 5380 and 9 more 2022-12-22 N/A 7.5 HIGH
A vulnerability exists in the Rockwell Automation controllers that allows a malformed CIP request to cause a major non-recoverable fault (MNRF) and a denial-of-service condition (DOS).
CVE-2022-46670 1 Rockwellautomation 10 Micrologix 1100, Micrologix 1100 Firmware, Micrologix 1400 and 7 more 2022-12-22 N/A 6.1 MEDIUM
Rockwell Automation was made aware of a vulnerability by a security researcher from Georgia Institute of Technology that the MicroLogix 1100 and 1400 controllers contain a vulnerability that may give an attacker the ability to accomplish remote code execution. The vulnerability is an unauthenticated stored cross-site scripting vulnerability in the embedded webserver. The payload is transferred to the controller over SNMP and is rendered on the homepage of the embedded website.
CVE-2017-14468 1 Rockwellautomation 2 Micrologix 1400, Micrologix 1400 B Firmware 2022-12-14 7.5 HIGH 9.8 CRITICAL
An exploitable access control vulnerability exists in the data, program, and function file permissions functionality of Allen Bradley Micrologix 1400 Series B FRN 21.2 and before. A specially crafted packet can cause a read or write operation resulting in disclosure of sensitive information, modification of settings, or modification of ladder logic. An attacker can send unauthenticated packets to trigger this vulnerability. Required Keyswitch State: REMOTE or PROG Description: This ability is leveraged in a larger exploit to flash custom firmware.
CVE-2017-14467 1 Rockwellautomation 2 Micrologix 1400, Micrologix 1400 B Firmware 2022-12-14 7.5 HIGH 9.8 CRITICAL
An exploitable access control vulnerability exists in the data, program, and function file permissions functionality of Allen Bradley Micrologix 1400 Series B FRN 21.2 and before. A specially crafted packet can cause a read or write operation resulting in disclosure of sensitive information, modification of settings, or modification of ladder logic. An attacker can send unauthenticated packets to trigger this vulnerability. Required Keyswitch State: REMOTE Description: Live rung edits are able to be made by an unauthenticated user allowing for addition, deletion, or modification of existing ladder logic. Additionally, faults and cpu state modification can be triggered if specific ladder logic is used.
CVE-2017-14465 1 Rockwellautomation 2 Micrologix 1400, Micrologix 1400 B Firmware 2022-12-14 7.5 HIGH 9.8 CRITICAL
An exploitable access control vulnerability exists in the data, program, and function file permissions functionality of Allen Bradley Micrologix 1400 Series B FRN 21.2 and before. A specially crafted packet can cause a read or write operation resulting in disclosure of sensitive information, modification of settings, or modification of ladder logic. An attacker can send unauthenticated packets to trigger this vulnerability. Required Keyswitch State: REMOTE Description: Any input or output can be forced, causing unpredictable activity from the PLC.
CVE-2017-14466 1 Rockwellautomation 2 Micrologix 1400, Micrologix 1400 B Firmware 2022-12-14 7.5 HIGH 9.8 CRITICAL
An exploitable access control vulnerability exists in the data, program, and function file permissions functionality of Allen Bradley Micrologix 1400 Series B FRN 21.2 and before. A specially crafted packet can cause a read or write operation resulting in disclosure of sensitive information, modification of settings, or modification of ladder logic. An attacker can send unauthenticated packets to trigger this vulnerability. Required Keyswitch State: REMOTE or PROG Description: The filetype 0x03 allows users write access, allowing the ability to overwrite the Master Password value stored in the file.
CVE-2017-14464 1 Rockwellautomation 2 Micrologix 1400, Micrologix 1400 B Firmware 2022-12-14 7.5 HIGH 9.8 CRITICAL
An exploitable access control vulnerability exists in the data, program, and function file permissions functionality of Allen Bradley Micrologix 1400 Series B FRN 21.2 and before. A specially crafted packet can cause a read or write operation resulting in disclosure of sensitive information, modification of settings, or modification of ladder logic. An attacker can send unauthenticated packets to trigger this vulnerability.Required Keyswitch State: REMOTE or PROG Associated Fault Code: 0001 Fault Type: Non-User Description: A fault state can be triggered by setting the NVRAM/memory module user program mismatch bit (S2:9) when a memory module is NOT installed.
CVE-2017-14463 1 Rockwellautomation 2 Micrologix 1400, Micrologix 1400 B Firmware 2022-12-14 7.5 HIGH 9.8 CRITICAL
An exploitable access control vulnerability exists in the data, program, and function file permissions functionality of Allen Bradley Micrologix 1400 Series B FRN 21.2 and before. A specially crafted packet can cause a read or write operation resulting in disclosure of sensitive information, modification of settings, or modification of ladder logic. An attacker can send unauthenticated packets to trigger this vulnerability. Required Keyswitch State: REMOTE or PROG Associated Fault Code: 0012 Fault Type: Non-User Description: A fault state can be triggered by overwriting the ladder logic data file (type 0x22 number 0x02) with null values.
CVE-2017-14462 1 Rockwellautomation 2 Micrologix 1400, Micrologix 1400 B Firmware 2022-12-14 7.5 HIGH 9.8 CRITICAL
An exploitable access control vulnerability exists in the data, program, and function file permissions functionality of Allen Bradley Micrologix 1400 Series B FRN 21.2 and before. A specially crafted packet can cause a read or write operation resulting in disclosure of sensitive information, modification of settings, or modification of ladder logic. An attacker can send unauthenticated packets to trigger this vulnerability. Required Keyswitch State: REMOTE or PROG (also RUN for some) Description: Allows an attacker to enable SNMP, Modbus, DNP, and any other features in the channel configuration. Also allows attackers to change network parameters, such as IP address, name server, and domain name.
CVE-2022-38744 1 Rockwellautomation 1 Factorytalk Alarms And Events 2022-10-31 N/A 7.5 HIGH
An unauthenticated attacker with network access to a victim's Rockwell Automation FactoryTalk Alarm and Events service could open a connection, causing the service to fault and become unavailable. The affected port could be used as a server ping port and uses messages structured with XML.
CVE-2021-32926 1 Rockwellautomation 4 Micro800, Micro800 Firmware, Micrologix 1400 and 1 more 2022-10-25 5.0 MEDIUM 7.5 HIGH
When an authenticated password change request takes place, this vulnerability could allow the attacker to intercept the message that includes the legitimate, new password hash and replace it with an illegitimate hash. The user would no longer be able to authenticate to the controller (Micro800: All versions, MicroLogix 1400: Version 21 and later) causing a denial-of-service condition
CVE-2020-25184 3 Rockwellautomation, Schneider-electric, Xylem 31 Aadvance Controller, Isagraf Free Runtime, Isagraf Runtime and 28 more 2022-10-21 2.1 LOW 5.5 MEDIUM
Rockwell Automation ISaGRAF Runtime Versions 4.x and 5.x stores the password in plaintext in a file that is in the same directory as the executable file. ISaGRAF Runtime reads the file and saves the data in a variable without any additional modification. A local, unauthenticated attacker could compromise the user passwords, resulting in information disclosure.
CVE-2022-3158 1 Rockwellautomation 1 Factorytalk Vantagepoint 2022-10-20 N/A 8.8 HIGH
Rockwell Automation FactoryTalk VantagePoint versions 8.0, 8.10, 8.20, 8.30, 8.31 are vulnerable to an input validation vulnerability. The FactoryTalk VantagePoint SQL Server lacks input validation when users enter SQL statements to retrieve information from the back-end database. If successfully exploited, this could allow a user with basic user privileges to perform remote code execution on the server.