CVE-2019-10954 1 Rockwellautomation 10 Armor Compact Guardlogix 5370, Armor Compact Guardlogix 5370 Firmware, Compact Guardlogix 5370 and 7 more 2021-10-28 7.8 HIGH 7.5 HIGH
An attacker could send crafted SMTP packets to cause a denial-of-service condition where the controller enters a major non-recoverable faulted state (MNRF) in CompactLogix 5370 L1, L2, and L3 Controllers, Compact GuardLogix 5370 controllers, and Armor Compact GuardLogix 5370 Controllers Versions 20 to 30.014 and earlier.
CVE-2020-12027 1 Rockwellautomation 1 Factorytalk View 2021-09-23 4.0 MEDIUM 4.3 MEDIUM
All versions of FactoryTalk View SE disclose the hostnames and file paths for certain files within the system. A remote, authenticated attacker may be able to leverage this information for reconnaissance efforts. Rockwell Automation recommends enabling built in security features found within FactoryTalk View SE. Users should follow guidance found in knowledge base articles 109056 and 1126943 to set up IPSec and/or HTTPs.
CVE-2020-12031 1 Rockwellautomation 1 Factorytalk View 2021-09-23 4.6 MEDIUM 7.8 HIGH
In all versions of FactoryTalk View SE, after bypassing memory corruption mechanisms found in the operating system, a local, authenticated attacker may corrupt the associated memory space allowing for arbitrary code execution. Rockwell Automation recommends applying patch 1126290. Before installing this patch, the patch rollup dated 06 Apr 2020 or later MUST be applied. 1066644 – Patch Roll-up for CPR9 SRx.
CVE-2020-12038 1 Rockwellautomation 5 Eds Subsystem, Rslinx, Rslinx Enterprise and 2 more 2021-09-23 4.3 MEDIUM 5.5 MEDIUM
Products that use EDS Subsystem: Version 28.0.1 and prior (FactoryTalk Linx software (Previously called RSLinx Enterprise): Versions 6.00, 6.10, and 6.11, RSLinx Classic: Version 4.11.00 and prior, RSNetWorx software: Version 28.00.00 and prior, Studio 5000 Logix Designer software: Version 32 and prior) is vulnerable. A memory corruption vulnerability exists in the algorithm that matches square brackets in the EDS subsystem. This may allow an attacker to craft specialized EDS files to crash the EDSParser COM object, leading to denial-of-service conditions.
CVE-2021-33012 1 Rockwellautomation 2 Micrologix 1100, Micrologix 1100 Firmware 2021-07-12 5.0 MEDIUM 8.6 HIGH
Rockwell Automation MicroLogix 1100, all versions, allows a remote, unauthenticated attacker sending specially crafted commands to cause the PLC to fault when the controller is switched to RUN mode, which results in a denial-of-service condition. If successfully exploited, this vulnerability will cause the controller to fault whenever the controller is switched to RUN mode.
CVE-2018-0163 2 Cisco, Rockwellautomation 96 1120 Connected Grid Router, 1240 Connected Grid Router, 1905 Serial Integrated Services Router and 93 more 2021-04-28 3.3 LOW 6.5 MEDIUM
A vulnerability in the 802.1x multiple-authentication (multi-auth) feature of Cisco IOS Software could allow an unauthenticated, adjacent attacker to bypass the authentication phase on an 802.1x multi-auth port. The vulnerability is due to a logic change error introduced into the code. An attacker could exploit this vulnerability by trying to access an 802.1x multi-auth port after a successful supplicant has authenticated. An exploit could allow the attacker to bypass the 802.1x access controls and obtain access to the network. Cisco Bug IDs: CSCvg69701.
CVE-2020-10642 1 Rockwellautomation 1 Rslinx Classic 2021-04-02 7.2 HIGH 7.8 HIGH
In Rockwell Automation RSLinx Classic versions 4.11.00 and prior, an authenticated local attacker could modify a registry key, which could lead to the execution of malicious code using system privileges when opening RSLinx Classic.
CVE-2021-22659 1 Rockwellautomation 2 Micrologix 1400, Micrologix 1400 Firmware 2021-03-31 7.5 HIGH 8.6 HIGH
Rockwell Automation MicroLogix 1400 Version 21.6 and below may allow a remote unauthenticated attacker to send a specially crafted Modbus packet allowing the attacker to retrieve or modify random values in the register. If successfully exploited, this may lead to a buffer overflow resulting in a denial-of-service condition. The FAULT LED will flash RED and communications may be lost. Recovery from denial-of-service condition requires the fault to be cleared by the user.
CVE-2020-14516 1 Rockwellautomation 1 Factorytalk Services Platform 2021-03-26 7.5 HIGH 10.0 CRITICAL
In Rockwell Automation FactoryTalk Services Platform Versions 6.10.00 and 6.11.00, there is an issue with the implementation of the SHA-256 hashing algorithm with FactoryTalk Services Platform that prevents the user password from being hashed properly.
CVE-2021-22665 1 Rockwellautomation 2 Drivetools Add-on Profiles, Drivetools Sp 2021-03-25 7.2 HIGH 7.8 HIGH
Rockwell Automation DriveTools SP v5.13 and below and Drives AOP v4.12 and below both contain a vulnerability that a local attacker with limited privileges may be able to exploit resulting in privilege escalation and complete control of the system.
CVE-2020-27265 4 Ge, Ptc, Rockwellautomation and 1 more 7 Industrial Gateway Server, Kepware Kepserverex, Opc-aggregator and 4 more 2021-01-21 7.5 HIGH 9.8 CRITICAL
KEPServerEX: v6.0 to v6.9, ThingWorx Kepware Server: v6.8 and v6.9, ThingWorx Industrial Connectivity: All versions, OPC-Aggregator: All versions, Rockwell Automation KEPServer Enterprise, GE Digital Industrial Gateway Server: v7.68.804 and v7.66, Software Toolbox TOP Server: All 6.x versions are vulnerable to a stack-based buffer overflow. Opening a specifically crafted OPC UA message could allow an attacker to crash the server and remotely execute code.
CVE-2020-27267 4 Ge, Ptc, Rockwellautomation and 1 more 7 Industrial Gateway Server, Kepware Kepserverex, Opc-aggregator and 4 more 2021-01-21 6.4 MEDIUM 9.1 CRITICAL
KEPServerEX v6.0 to v6.9, ThingWorx Kepware Server v6.8 and v6.9, ThingWorx Industrial Connectivity (all versions), OPC-Aggregator (all versions), Rockwell Automation KEPServer Enterprise, GE Digital Industrial Gateway Server v7.68.804 and v7.66, and Software Toolbox TOP Server all 6.x versions, are vulnerable to a heap-based buffer overflow. Opening a specifically crafted OPC UA message could allow an attacker to crash the server and potentially leak data.
CVE-2020-27263 4 Ge, Ptc, Rockwellautomation and 1 more 7 Industrial Gateway Server, Kepware Kepserverex, Opc-aggregator and 4 more 2021-01-21 6.4 MEDIUM 9.1 CRITICAL
KEPServerEX: v6.0 to v6.9, ThingWorx Kepware Server: v6.8 and v6.9, ThingWorx Industrial Connectivity: All versions, OPC-Aggregator: All versions, Rockwell Automation KEPServer Enterprise, GE Digital Industrial Gateway Server: v7.68.804 and v7.66, Software Toolbox TOP Server: All 6.x versions, are vulnerable to a heap-based buffer overflow. Opening a specifically crafted OPC UA message could allow an attacker to crash the server and potentially leak data.
CVE-2020-5806 1 Rockwellautomation 1 Factorytalk Linx 2020-12-30 2.1 LOW 5.5 MEDIUM
An attacker-controlled memory allocation size can be passed to the C++ new operator in the CServerManager::HandleBrowseLoadIconStreamRequest in messaging.dll. This can be done by sending a specially crafted message to 127.0.0.1:7153. Observed in FactoryTalk Linx 6.11. All versions of FactoryTalk Linx are affected.
CVE-2020-5807 1 Rockwellautomation 1 Factorytalk Diagnostics 2020-12-30 5.0 MEDIUM 7.5 HIGH
An unauthenticated remote attacker can send data to RsvcHost.exe listening on TCP port 5241 to add entries in the FactoryTalk Diagnostics event log. The attacker can specify long fields in the log entry, which can cause an unhandled exception in wcscpy_s() if a local user opens FactoryTalk Diagnostics Viewer (FTDiagViewer.exe) to view the log entry. Observed in FactoryTalk Diagnostics 6.11. All versions of FactoryTalk Diagnostics are affected.
CVE-2020-5801 1 Rockwellautomation 1 Factorytalk Linx 2020-12-30 5.0 MEDIUM 7.5 HIGH
An attacker can craft and send an OpenNamespace message to port 4241 with valid session-id that triggers an unhandled exception in CFTLDManager::HandleRequest function in RnaDaSvr.dll, resulting in process termination. Observed in FactoryTalk Linx 6.11. All versions of FactoryTalk Linx are affected.
CVE-2020-12025 1 Rockwellautomation 1 Studio 5000 Logix Designer 2020-12-15 4.3 MEDIUM 3.3 LOW
Rockwell Automation Logix Designer Studio 5000 Versions 32.00, 32.01, and 32.02 vulnerable to an xml external entity (XXE) vulnerability, which may allow an attacker to view hostnames or other resources from the program.
CVE-2020-27255 1 Rockwellautomation 1 Factorytalk Linx 2020-11-30 5.0 MEDIUM 7.5 HIGH
A heap overflow vulnerability exists within FactoryTalk Linx Version 6.11 and prior. This vulnerability could allow a remote, unauthenticated attacker to send malicious set attribute requests, which could result in the leaking of sensitive information. This information disclosure could lead to the bypass of address space layout randomization (ASLR).
CVE-2020-27253 1 Rockwellautomation 1 Factorytalk Linx 2020-11-30 7.8 HIGH 7.5 HIGH
A flaw exists in the Ingress/Egress checks routine of FactoryTalk Linx Version 6.11 and prior. This vulnerability could allow a remote, unauthenticated attacker to specifically craft a malicious packet resulting in a denial-of-service condition on the device.
CVE-2020-27251 1 Rockwellautomation 1 Factorytalk Linx 2020-11-30 7.5 HIGH 9.8 CRITICAL
A heap overflow vulnerability exists within FactoryTalk Linx Version 6.11 and prior. This vulnerability could allow a remote, unauthenticated attacker to send malicious port ranges, which could result in remote code execution.