An exploitable access control vulnerability exists in the data, program, and function file permissions functionality of Allen Bradley Micrologix 1400 Series B FRN 21.2 and before. A specially crafted packet can cause a read or write operation resulting in disclosure of sensitive information, modification of settings, or modification of ladder logic. An attacker can send unauthenticated packets to trigger this vulnerability.Required Keyswitch State: REMOTE or PROG Associated Fault Code: 0001 Fault Type: Non-User Description: A fault state can be triggered by setting the NVRAM/memory module user program mismatch bit (S2:9) when a memory module is NOT installed.
References
Link | Resource |
---|---|
https://www.talosintelligence.com/vulnerability_reports/TALOS-2017-0443 | Exploit Third Party Advisory |
Configurations
Configuration 1 (hide)
AND |
|
Information
Published : 2018-04-05 14:29
Updated : 2022-12-14 08:27
NVD link : CVE-2017-14464
Mitre link : CVE-2017-14464
JSON object : View
CWE
Products Affected
rockwellautomation
- micrologix_1400_b_firmware
- micrologix_1400