Vulnerabilities (CVE)

Join the Common Vulnerabilities and Exposures (CVE) community and start to get notified about new vulnerabilities.

Filtered by vendor Siemens Subscribe
Filtered by product Nucleus Readystart
Total 3 CVE
CVE Vendors Products Updated CVSS v2 CVSS v3
CVE-2020-28388 4 Arm, Mips, Powerpc Project and 1 more 8 Arm, Mips, Powerpc and 5 more 2022-12-13 5.0 MEDIUM 5.3 MEDIUM
A vulnerability has been identified in APOGEE PXC Series (BACnet) (All versions < V3.5.5), APOGEE PXC Series (P2 Ethernet) (All versions < V2.8.20), Nucleus NET (All versions < V5.2), Nucleus ReadyStart V3 (All versions < V2012.12), Nucleus Source Code (All versions), PLUSCONTROL 1st Gen (All versions), TALON TC Series (BACnet) (All versions < V3.5.5). Initial Sequence Numbers (ISNs) for TCP connections are derived from an insufficiently random source. As a result, the ISN of current and future TCP connections could be predictable. An attacker could hijack existing sessions or spoof future ones.
CVE-2019-13939 1 Siemens 20 Apogee Modular Building Controller, Apogee Modular Building Controller Firmware, Apogee Modular Equiment Controller and 17 more 2022-05-20 4.8 MEDIUM 7.1 HIGH
A vulnerability has been identified in APOGEE MEC/MBC/PXC (P2) (All versions < V2.8.2), APOGEE PXC Series (BACnet) (All versions < V3.5.3), APOGEE PXC Series (P2) (All versions >= V2.8.2 and < V2.8.19), Desigo PXC00-E.D (All versions >= V2.3x and < V6.00.327), Desigo PXC00-U (All versions >= V2.3x and < V6.00.327), Desigo PXC001-E.D (All versions >= V2.3x and < V6.00.327), Desigo PXC100-E.D (All versions >= V2.3x and < V6.00.327), Desigo PXC12-E.D (All versions >= V2.3x and < V6.00.327), Desigo PXC128-U (All versions >= V2.3x and < V6.00.327), Desigo PXC200-E.D (All versions >= V2.3x and < V6.00.327), Desigo PXC22-E.D (All versions >= V2.3x and < V6.00.327), Desigo PXC22.1-E.D (All versions >= V2.3x and < V6.00.327), Desigo PXC36.1-E.D (All versions >= V2.3x and < V6.00.327), Desigo PXC50-E.D (All versions >= V2.3x and < V6.00.327), Desigo PXC64-U (All versions >= V2.3x and < V6.00.327), Desigo PXM20-E (All versions >= V2.3x and < V6.00.327), Nucleus NET (All versions), Nucleus RTOS (All versions), Nucleus ReadyStart for ARM, MIPS, and PPC (All versions < V2017.02.2 with patch "Nucleus 2017.02.02 Nucleus NET Patch"), Nucleus SafetyCert (All versions), Nucleus Source Code (All versions), SIMOTICS CONNECT 400 (All versions < V0.3.0.330), TALON TC Series (BACnet) (All versions < V3.5.3), VSTAR (All versions). By sending specially crafted DHCP packets to a device where the DHCP client is enabled, an attacker could change the IP address of the device to an invalid value. The vulnerability could affect availability and integrity of the device. Adjacent network access is required, but no authentication and no user interaction is needed to conduct an attack.
CVE-2021-25663 1 Siemens 4 Capital Vstar, Nucleus Net, Nucleus Readystart and 1 more 2021-12-10 5.0 MEDIUM 7.5 HIGH
A vulnerability has been identified in Capital VSTAR (Versions including affected IPv6 stack), Nucleus NET (All versions), Nucleus ReadyStart V3 (All versions < V2017.02.4), Nucleus ReadyStart V4 (All versions < V4.1.0), Nucleus Source Code (Versions including affected IPv6 stack). The function that processes IPv6 headers does not check the lengths of extension header options, allowing attackers to put this function into an infinite loop with crafted length values.