CVE | Vendors | Products | Updated | CVSS v2 | CVSS v3 |
---|---|---|---|---|---|
CVE-2022-25622 | 1 Siemens | 23 Simatic Cfu Diq, Simatic Cfu Diq Firmware, Simatic Cfu Pa and 20 more | 2023-02-14 | 5.0 MEDIUM | 7.5 HIGH |
A vulnerability has been identified in SIMATIC CFU DIQ, SIMATIC CFU PA, SIMATIC ET 200pro IM154-8 PN/DP CPU, SIMATIC ET 200pro IM154-8F PN/DP CPU, SIMATIC ET 200pro IM154-8FX PN/DP CPU, SIMATIC ET 200S IM151-8 PN/DP CPU, SIMATIC ET 200S IM151-8F PN/DP CPU, SIMATIC ET200AL IM157-1 PN, SIMATIC ET200ecoPN, AI 8xRTD/TC, M12-L, SIMATIC ET200ecoPN, CM 4x IO-Link, M12-L, SIMATIC ET200ecoPN, CM 8x IO-Link, M12-L, SIMATIC ET200ecoPN, CM 8x IO-Link, M12-L, SIMATIC ET200ecoPN, DI 16x24VDC, M12-L, SIMATIC ET200ecoPN, DI 8x24VDC, M12-L, SIMATIC ET200ecoPN, DIQ 16x24VDC/2A, M12-L, SIMATIC ET200ecoPN, DQ 8x24VDC/0,5A, M12-L, SIMATIC ET200ecoPN, DQ 8x24VDC/2A, M12-L, SIMATIC ET200MP IM155-5 PN HF (incl. SIPLUS variants), SIMATIC ET200SP IM155-6 MF HF, SIMATIC ET200SP IM155-6 PN HA (incl. SIPLUS variants), SIMATIC ET200SP IM155-6 PN HF (incl. SIPLUS variants), SIMATIC ET200SP IM155-6 PN/2 HF (incl. SIPLUS variants), SIMATIC ET200SP IM155-6 PN/3 HF (incl. SIPLUS variants), SIMATIC PN/MF Coupler, SIMATIC PN/PN Coupler, SIMATIC S7-1500 CPU family (incl. related ET200 CPUs and SIPLUS variants), SIMATIC S7-300 CPU 314C-2 PN/DP, SIMATIC S7-300 CPU 315-2 PN/DP, SIMATIC S7-300 CPU 315F-2 PN/DP, SIMATIC S7-300 CPU 315T-3 PN/DP, SIMATIC S7-300 CPU 317-2 PN/DP, SIMATIC S7-300 CPU 317F-2 PN/DP, SIMATIC S7-300 CPU 317T-3 PN/DP, SIMATIC S7-300 CPU 317TF-3 PN/DP, SIMATIC S7-300 CPU 319-3 PN/DP, SIMATIC S7-300 CPU 319F-3 PN/DP, SIMATIC S7-400 H V6 CPU family (incl. SIPLUS variants), SIMATIC S7-400 PN/DP V7 CPU family (incl. SIPLUS variants), SIMATIC S7-410 V10 CPU family (incl. SIPLUS variants), SIMATIC S7-410 V8 CPU family (incl. SIPLUS variants), SIMATIC TDC CP51M1, SIMATIC TDC CPU555, SIMATIC WinAC RTX 2010, SIMATIC WinAC RTX F 2010, SINAMICS DCM, SINAMICS G110M, SINAMICS G115D, SINAMICS G120 (incl. SIPLUS variants), SINAMICS G130, SINAMICS G150, SINAMICS S110, SINAMICS S120 (incl. SIPLUS variants), SINAMICS S150, SINAMICS S210, SINAMICS V90, SIPLUS ET 200S IM151-8 PN/DP CPU, SIPLUS ET 200S IM151-8F PN/DP CPU, SIPLUS HCS4200 CIM4210, SIPLUS HCS4200 CIM4210C, SIPLUS HCS4300 CIM4310, SIPLUS NET PN/PN Coupler, SIPLUS S7-300 CPU 314C-2 PN/DP, SIPLUS S7-300 CPU 315-2 PN/DP, SIPLUS S7-300 CPU 315F-2 PN/DP, SIPLUS S7-300 CPU 317-2 PN/DP, SIPLUS S7-300 CPU 317F-2 PN/DP. The PROFINET (PNIO) stack, when integrated with the Interniche IP stack, improperly handles internal resources for TCP segments where the minimum TCP-Header length is less than defined. This could allow an attacker to create a denial of service condition for TCP services on affected devices by sending specially crafted TCP segments. | |||||
CVE-2018-16556 | 1 Siemens | 10 Simatic S7-400, Simatic S7-400 Firmware, Simatic S7-400 Pn\/dp V7 and 7 more | 2023-01-10 | 7.8 HIGH | 7.5 HIGH |
A vulnerability has been identified in SIMATIC S7-400 H V4.5 and below CPU family (incl. SIPLUS variants) (All versions), SIMATIC S7-400 H V6 CPU family (incl. SIPLUS variants) (All versions < V6.0.9), SIMATIC S7-400 PN/DP V6 and below CPU family (incl. SIPLUS variants) (All versions), SIMATIC S7-400 PN/DP V7 CPU family (incl. SIPLUS variants) (All versions), SIMATIC S7-410 CPU family (incl. SIPLUS variants) (All versions < V8.2.1). Specially crafted packets sent to port 102/tcp via Ethernet interface, via PROFIBUS, or via Multi Point Interfaces (MPI) could cause the affected devices to go into defect mode. Manual reboot is required to resume normal operation. Successful exploitation requires an attacker to be able to send specially crafted packets to port 102/tcp via Ethernet interface, via PROFIBUS or Multi Point Interfaces (MPI). No user interaction and no user privileges are required to exploit the security vulnerability. The vulnerability could allow causing a denial of service condition of the core functionality of the CPU, compromising the availability of the system. | |||||
CVE-2018-4843 | 1 Siemens | 22 Simatic Cp 343-1, Simatic Cp 343-1 Firmware, Simatic Cp 443-1 and 19 more | 2023-01-10 | 6.1 MEDIUM | 6.5 MEDIUM |
A vulnerability has been identified in SIMATIC CP 343-1 (incl. SIPLUS variants) (All versions), SIMATIC CP 343-1 Advanced (incl. SIPLUS variants) (All versions), SIMATIC CP 443-1 (incl. SIPLUS variants) (All versions), SIMATIC CP 443-1 Advanced (incl. SIPLUS variants) (All versions), SIMATIC ET 200pro IM154-8 PN/DP CPU (All versions < V3.2.16), SIMATIC ET 200pro IM154-8F PN/DP CPU (All versions < V3.2.16), SIMATIC ET 200pro IM154-8FX PN/DP CPU (All versions < V3.2.16), SIMATIC ET 200S IM151-8 PN/DP CPU (All versions < V3.2.16), SIMATIC ET 200S IM151-8F PN/DP CPU (All versions < V3.2.16), SIMATIC S7-1500 CPU family (incl. related ET200 CPUs and SIPLUS variants) (All versions < V1.7.0), SIMATIC S7-1500 Software Controller (All versions < V1.7.0), SIMATIC S7-300 CPU 314C-2 PN/DP (All versions < V3.3.16), SIMATIC S7-300 CPU 315-2 PN/DP (All versions < V3.2.16), SIMATIC S7-300 CPU 315F-2 PN/DP (All versions < V3.2.16), SIMATIC S7-300 CPU 315T-3 PN/DP (All versions < V3.2.16), SIMATIC S7-300 CPU 317-2 PN/DP (All versions < V3.2.16), SIMATIC S7-300 CPU 317F-2 PN/DP (All versions < V3.2.16), SIMATIC S7-300 CPU 317T-3 PN/DP (All versions < V3.2.16), SIMATIC S7-300 CPU 317TF-3 PN/DP (All versions < V3.2.16), SIMATIC S7-300 CPU 319-3 PN/DP (All versions < V3.2.16), SIMATIC S7-300 CPU 319F-3 PN/DP (All versions < V3.2.16), SIMATIC S7-400 H V6 CPU family (incl. SIPLUS variants) (All versions < V6.0.9), SIMATIC S7-400 PN/DP V6 CPU family (incl. SIPLUS variants) (All versions < V6.0.7), SIMATIC S7-400 PN/DP V7 CPU family (incl. SIPLUS variants) (All versions), SIMATIC S7-410 CPU family (incl. SIPLUS variants) (All versions < V8.1), SIMATIC WinAC RTX 2010 (All versions < V2010 SP3), SIMATIC WinAC RTX F 2010 (All versions < V2010 SP3), SINUMERIK 828D (All versions < V4.7 SP6 HF1), SIPLUS ET 200S IM151-8 PN/DP CPU (All versions < V3.2.16), SIPLUS ET 200S IM151-8F PN/DP CPU (All versions < V3.2.16), SIPLUS S7-300 CPU 314C-2 PN/DP (All versions < V3.3.16), SIPLUS S7-300 CPU 315-2 PN/DP (All versions < V3.2.16), SIPLUS S7-300 CPU 315F-2 PN/DP (All versions < V3.2.16), SIPLUS S7-300 CPU 317-2 PN/DP (All versions < V3.2.16), SIPLUS S7-300 CPU 317F-2 PN/DP (All versions < V3.2.16), Softnet PROFINET IO for PC-based Windows systems (All versions). Responding to a PROFINET DCP request with a specially crafted PROFINET DCP packet could cause a Denial-of-Service condition of the requesting system. The security vulnerability could be exploited by an attacker located on the same Ethernet segment (OSI Layer 2) as the targeted device. Successful exploitation requires no user interaction or privileges and impacts the availability of core functionality of the affected device. A manual restart is required to recover the system. At the time of advisory publication no public exploitation of this security vulnerability is known. Siemens provides mitigations to resolve the security issue. PROFIBUS interfaces are not affected. | |||||
CVE-2018-16557 | 1 Siemens | 8 Simatic S7-400, Simatic S7-400 Firmware, Simatic S7-400 Pn\/dp V7 and 5 more | 2023-01-10 | 7.8 HIGH | 7.5 HIGH |
A vulnerability has been identified in SIMATIC S7-400 H V4.5 and below CPU family (incl. SIPLUS variants) (All versions), SIMATIC S7-400 H V6 CPU family (incl. SIPLUS variants) (All versions < V6.0.9), SIMATIC S7-400 PN/DP V6 and below CPU family (incl. SIPLUS variants) (All versions), SIMATIC S7-400 PN/DP V7 CPU family (incl. SIPLUS variants) (All versions), SIMATIC S7-410 CPU family (incl. SIPLUS variants) (All versions < V8.2.1). Sending of specially crafted packets to port 102/tcp via Ethernet interface via PROFIBUS or Multi Point Interfaces (MPI) could cause a denial of service condition on affected devices. Flashing with a firmware image may be required to recover the CPU. Successful exploitation requires an attacker to have network access to port 102/tcp via Ethernet interface or to be able to send messages via PROFIBUS or Multi Point Interfaces (MPI) to the device. No user interaction is required. If no access protection is configured, no privileges are required to exploit the security vulnerability. The vulnerability could allow causing a denial of service condition of the core functionality of the CPU, compromising the availability of the system. | |||||
CVE-2022-30694 | 1 Siemens | 223 6ag1151-8ab01-7ab0, 6ag1151-8ab01-7ab0 Firmware, 6ag1151-8fb01-2ab0 and 220 more | 2023-01-10 | N/A | 3.5 LOW |
A vulnerability has been identified in SIMATIC Drive Controller family (All versions < V3.0.1), SIMATIC ET 200pro IM154-8 PN/DP CPU (All versions < V3.2.19), SIMATIC ET 200pro IM154-8F PN/DP CPU (All versions < V3.2.19), SIMATIC ET 200pro IM154-8FX PN/DP CPU (All versions < V3.2.19), SIMATIC ET 200S IM151-8 PN/DP CPU (All versions < V3.2.19), SIMATIC ET 200S IM151-8F PN/DP CPU (All versions < V3.2.19), SIMATIC PC Station (All versions >= V2.1), SIMATIC S7-1200 CPU family (incl. SIPLUS variants) (All versions < V4.6.0), SIMATIC S7-1500 CPU family (incl. related ET200 CPUs and SIPLUS variants) (All versions < V3.0.1), SIMATIC S7-1500 Software Controller (All versions), SIMATIC S7-300 CPU 314C-2 PN/DP (All versions < V3.3.19), SIMATIC S7-300 CPU 315-2 PN/DP (All versions < V3.2.19), SIMATIC S7-300 CPU 315F-2 PN/DP (All versions < V3.2.19), SIMATIC S7-300 CPU 315T-3 PN/DP (All versions < V3.2.19), SIMATIC S7-300 CPU 317-2 PN/DP (All versions < V3.2.19), SIMATIC S7-300 CPU 317F-2 PN/DP (All versions < V3.2.19), SIMATIC S7-300 CPU 317T-3 PN/DP (All versions < V3.2.19), SIMATIC S7-300 CPU 317TF-3 PN/DP (All versions < V3.2.19), SIMATIC S7-300 CPU 319-3 PN/DP (All versions < V3.2.19), SIMATIC S7-300 CPU 319F-3 PN/DP (All versions < V3.2.19), SIMATIC S7-400 PN/DP V6 CPU family (incl. SIPLUS variants) (All versions), SIMATIC S7-400 PN/DP V7 CPU family (incl. SIPLUS variants) (All versions), SIMATIC S7-PLCSIM Advanced (All versions < V5.0), SIMATIC WinCC Runtime Advanced (All versions), SINUMERIK ONE (All versions), SIPLUS ET 200S IM151-8 PN/DP CPU (All versions < V3.2.19), SIPLUS ET 200S IM151-8F PN/DP CPU (All versions < V3.2.19), SIPLUS S7-300 CPU 314C-2 PN/DP (All versions < V3.3.19), SIPLUS S7-300 CPU 315-2 PN/DP (All versions < V3.2.19), SIPLUS S7-300 CPU 315F-2 PN/DP (All versions < V3.2.19), SIPLUS S7-300 CPU 317-2 PN/DP (All versions < V3.2.19), SIPLUS S7-300 CPU 317F-2 PN/DP (All versions < V3.2.19). The login endpoint /FormLogin in affected web services does not apply proper origin checking. This could allow authenticated remote attackers to track the activities of other users via a login cross-site request forgery attack. | |||||
CVE-2021-40368 | 1 Siemens | 8 Simatic S7-400 Pn\/dp V7, Simatic S7-400 Pn\/dp V7 Firmware, Simatic S7-400h V6 and 5 more | 2022-08-10 | 5.0 MEDIUM | 7.5 HIGH |
A vulnerability has been identified in SIMATIC S7-400 H V6 CPU family (incl. SIPLUS variants) (All versions < V6.0.10), SIMATIC S7-400 PN/DP V7 CPU family (incl. SIPLUS variants) (All versions), SIMATIC S7-410 V10 CPU family (incl. SIPLUS variants) (All versions < V10.1), SIMATIC S7-410 V8 CPU family (incl. SIPLUS variants) (All versions < V8.2.3). Affected devices improperly handle specially crafted packets sent to port 102/tcp. This could allow an attacker to create a Denial-of-Service condition. A restart is needed to restore normal operations. |