Vulnerabilities (CVE)

Join the Common Vulnerabilities and Exposures (CVE) community and start to get notified about new vulnerabilities.

Filtered by vendor Siemens Subscribe
Filtered by product Logo\!8 Bm Firmware
Total 3 CVE
CVE Vendors Products Updated CVSS v2 CVSS v3
CVE-2019-10921 1 Siemens 2 Logo\!8 Bm, Logo\!8 Bm Firmware 2022-01-04 5.0 MEDIUM 7.5 HIGH
A vulnerability has been identified in LOGO! 8 BM (incl. SIPLUS variants) (All versions < V8.3). Unencrypted storage of passwords in the project could allow an attacker with access to port 10005/tcp to obtain passwords of the device. The security vulnerability could be exploited by an unauthenticated attacker with network access to port 10005/tcp. No user interaction is required to exploit this security vulnerability. The vulnerability impacts confidentiality of the device. At the time of advisory publication no public exploitation of this security vulnerability was known
CVE-2019-10919 1 Siemens 2 Logo\!8 Bm, Logo\!8 Bm Firmware 2022-01-04 7.5 HIGH 9.4 CRITICAL
A vulnerability has been identified in LOGO! 8 BM (incl. SIPLUS variants) (All versions < V8.3). Attackers with access to port 10005/tcp could perform device reconfigurations and obtain project files from the devices. The system manual recommends to protect access to this port. The security vulnerability could be exploited by an unauthenticated attacker with network access to port 10005/tcp. No user interaction is required to exploit this security vulnerability. The vulnerability impacts confidentiality, integrity, and availability of the device. At the time of advisory publication no public exploitation of this security vulnerability was known.
CVE-2019-10920 1 Siemens 2 Logo\!8 Bm, Logo\!8 Bm Firmware 2022-01-04 5.0 MEDIUM 7.5 HIGH
A vulnerability has been identified in LOGO! 8 BM (incl. SIPLUS variants) (All versions < V8.3). Project data stored on the device, which is accessible via port 10005/tcp, can be decrypted due to a hardcoded encryption key. The security vulnerability could be exploited by an unauthenticated attacker with network access to port 10005/tcp. No user interaction is required to exploit this security vulnerability. The vulnerability impacts confidentiality of the device. At the time of advisory publication no public exploitation of this security vulnerability was known.