Vulnerabilities (CVE)

Join the Common Vulnerabilities and Exposures (CVE) community and start to get notified about new vulnerabilities.

Filtered by vendor Rockwellautomation Subscribe
Filtered by product Factorytalk Services Platform
Total 10 CVE
CVE Vendors Products Updated CVSS v2 CVSS v3
CVE-2021-22681 1 Rockwellautomation 20 Compact Guardlogix 5370, Compact Guardlogix 5380, Compactlogix 1768 and 17 more 2022-04-25 7.5 HIGH 9.8 CRITICAL
Rockwell Automation Studio 5000 Logix Designer Versions 21 and later, and RSLogix 5000 Versions 16 through 20 use a key to verify Logix controllers are communicating with Rockwell Automation CompactLogix 1768, 1769, 5370, 5380, 5480: ControlLogix 5550, 5560, 5570, 5580; DriveLogix 5560, 5730, 1794-L34; Compact GuardLogix 5370, 5380; GuardLogix 5570, 5580; SoftLogix 5800. Rockwell Automation Studio 5000 Logix Designer Versions 21 and later and RSLogix 5000: Versions 16 through 20 are vulnerable because an unauthenticated attacker could bypass this verification mechanism and authenticate with Rockwell Automation CompactLogix 1768, 1769, 5370, 5380, 5480: ControlLogix 5550, 5560, 5570, 5580; DriveLogix 5560, 5730, 1794-L34; Compact GuardLogix 5370, 5380; GuardLogix 5570, 5580; SoftLogix 5800.
CVE-2021-32960 1 Rockwellautomation 1 Factorytalk Services Platform 2022-04-12 6.0 MEDIUM 8.8 HIGH
Rockwell Automation FactoryTalk Services Platform v6.11 and earlier, if FactoryTalk Security is enabled and deployed contains a vulnerability that may allow a remote, authenticated attacker to bypass FactoryTalk Security policies based on the computer name. If successfully exploited, this may allow an attacker to have the same privileges as if they were logged on to the client machine.
CVE-2020-14478 1 Rockwellautomation 1 Factorytalk Services Platform 2022-03-04 5.6 MEDIUM 7.1 HIGH
A local, authenticated attacker could use an XML External Entity (XXE) attack to exploit weakly configured XML files to access local or remote content. A successful exploit could potentially cause a denial-of-service condition and allow the attacker to arbitrarily read any local file via system-level services.
CVE-2020-14516 1 Rockwellautomation 1 Factorytalk Services Platform 2021-03-26 7.5 HIGH 10.0 CRITICAL
In Rockwell Automation FactoryTalk Services Platform Versions 6.10.00 and 6.11.00, there is an issue with the implementation of the SHA-256 hashing algorithm with FactoryTalk Services Platform that prevents the user password from being hashed properly.
CVE-2020-12033 1 Rockwellautomation 1 Factorytalk Services Platform 2020-07-06 5.8 MEDIUM 8.8 HIGH
In Rockwell Automation FactoryTalk Services Platform, all versions, the redundancy host service (RdcyHost.exe) does not validate supplied identifiers, which could allow an unauthenticated, adjacent attacker to execute remote COM objects with elevated privileges.
CVE-2020-6967 1 Rockwellautomation 1 Factorytalk Services Platform 2020-03-27 10.0 HIGH 9.8 CRITICAL
In Rockwell Automation all versions of FactoryTalk Diagnostics software, a subsystem of the FactoryTalk Services Platform, FactoryTalk Diagnostics exposes a .NET Remoting endpoint via RNADiagnosticsSrv.exe at TCPtcp/8082, which can insecurely deserialize untrusted data.
CVE-2018-18981 1 Rockwellautomation 1 Factorytalk Services Platform 2019-10-09 7.8 HIGH 7.5 HIGH
In Rockwell Automation FactoryTalk Services Platform 2.90 and earlier, a remote unauthenticated attacker could send numerous crafted packets to service ports resulting in memory consumption that could lead to a partial or complete denial-of-service condition to the affected services.
CVE-2014-9209 1 Rockwellautomation 2 Factorytalk Services Platform, Factorytalk View Studio 2015-03-31 6.9 MEDIUM N/A
Untrusted search path vulnerability in the Clean Utility application in Rockwell Automation FactoryTalk Services Platform before 2.71.00 and FactoryTalk View Studio 8.00.00 and earlier allows local users to gain privileges via a Trojan horse DLL in an unspecified directory.
CVE-2012-4713 1 Rockwellautomation 1 Factorytalk Services Platform 2013-04-17 7.8 HIGH N/A
Integer signedness error in RNADiagnostics.dll in Rockwell Automation FactoryTalk Services Platform (FTSP) CPR9, CPR9-SR1, CPR9-SR2, CPR9-SR3, CPR9-SR4, CPR9-SR5, CPR9-SR5.1, and CPR9-SR6 allows remote attackers to cause a denial of service (service outage or RNADiagReceiver.exe daemon crash) via UDP data that specifies a negative integer value.
CVE-2012-4714 1 Rockwellautomation 1 Factorytalk Services Platform 2013-04-17 7.8 HIGH N/A
Integer overflow in RNADiagnostics.dll in Rockwell Automation FactoryTalk Services Platform (FTSP) CPR9, CPR9-SR1, CPR9-SR2, CPR9-SR3, CPR9-SR4, CPR9-SR5, CPR9-SR5.1, and CPR9-SR6 allows remote attackers to cause a denial of service (service outage or RNADiagReceiver.exe daemon crash) via UDP data that specifies a large integer value.