Vulnerabilities (CVE)

Join the Common Vulnerabilities and Exposures (CVE) community and start to get notified about new vulnerabilities.

Filtered by vendor Siemens Subscribe
Filtered by product Scalance X200 Irt
Total 3 CVE
CVE Vendors Products Updated CVSS v2 CVSS v3
CVE-2018-4842 1 Siemens 6 Scalance X200, Scalance X200 Firmware, Scalance X200 Irt and 3 more 2022-12-13 3.5 LOW 4.8 MEDIUM
A vulnerability has been identified in SCALANCE X-200IRT switch family (incl. SIPLUS NET variants) (All versions < V5.4.1), SCALANCE X-200RNA switch family (All versions < V3.2.7), SCALANCE X-300 switch family (incl. X408 and SIPLUS NET variants) (All versions < V4.1.3). A remote, authenticated attacker with access to the configuration web server could be able to store script code on the web site, if the HRP redundancy option is set. This code could be executed in the web browser of victims visiting this web site (XSS), affecting its confidentiality, integrity and availability. User interaction is required for successful exploitation, as the user needs to visit the manipulated web site. At the stage of publishing this security advisory no public exploitation is known. The vendor has confirmed the vulnerability and provides mitigations to resolve it.
CVE-2017-2680 1 Siemens 183 S110 Pn, Dk Standard Ethernet Controller, Dk Standard Ethernet Controller Firmware and 180 more 2022-04-12 6.1 MEDIUM 6.5 MEDIUM
Specially crafted PROFINET DCP broadcast packets could cause a denial of service condition of affected products on a local Ethernet segment (Layer 2). Human interaction is required to recover the systems. PROFIBUS interfaces are not affected.
CVE-2017-2681 1 Siemens 155 Dk Standard Ethernet Controller, Dk Standard Ethernet Controller Firmware, Ek-ertec 200 Pn Io and 152 more 2022-04-12 6.1 MEDIUM 6.5 MEDIUM
Specially crafted PROFINET DCP packets sent on a local Ethernet segment (Layer 2) to an affected product could cause a denial of service condition of that product. Human interaction is required to recover the system. PROFIBUS interfaces are not affected. This vulnerability affects only SIMATIC HMI Multi Panels and HMI Mobile Panels, and S7-300/S7-400 devices.