CVE | Vendors | Products | Updated | CVSS v2 | CVSS v3 |
---|---|---|---|---|---|
CVE-2022-45788 | 1 Schneider-electric | 108 Ecostruxure Control Expert, Ecostruxure Process Expert, Modicon M340 Bmxp341000 and 105 more | 2023-02-08 | N/A | 9.8 CRITICAL |
A CWE-754: Improper Check for Unusual or Exceptional Conditions vulnerability exists that could cause arbitrary code execution, denial of service and loss of confidentiality & integrity when a malicious project file is loaded onto the controller. Affected Products: EcoStruxure™ Control Expert (All Versions), EcoStruxure™ Process Expert (Versions prior to V2020), Modicon M340 CPU - part numbers BMXP34* (All Versions), Modicon M580 CPU - part numbers BMEP* and BMEH* (All Versions), Modicon M580 CPU Safety - part numbers BMEP58*S and BMEH58*S (All Versions), Modicon Momentum Unity M1E Processor - 171CBU* (All Versions), Modicon MC80 - BMKC80 (All Versions), Legacy Modicon Quantum - 140CPU65* and Premium CPUs - TSXP57* (All Versions) | |||||
CVE-2021-22786 | 1 Schneider-electric | 82 Modicon M340 Bmxp341000, Modicon M340 Bmxp341000 Firmware, Modicon M340 Bmxp342000 and 79 more | 2023-02-08 | N/A | 7.5 HIGH |
A CWE-200: Information Exposure vulnerability exists that could cause the exposure of sensitive information stored on the memory of the controller when communicating over the Modbus TCP protocol. Affected Products: Modicon M340 CPU (part numbers BMXP34*) (Versions prior to V3.30), Modicon M580 CPU (part numbers BMEP* and BMEH*) (Versions prior to SV3.20), Modicon MC80 (BMKC80) (Versions prior to V1.6), Modicon M580 CPU Safety (part numbers BMEP58*S and BMEH58*S) (All Versions), Modicon Momentum MDI (171CBU*) (Versions prior to V2.3), Legacy Modicon Quantum (All Versions) | |||||
CVE-2022-45789 | 1 Schneider-electric | 72 Ecostruxure Control Expert, Ecostruxure Process Expert, Modicon M340 Bmxp341000 and 69 more | 2023-02-07 | N/A | 9.8 CRITICAL |
A CWE-294: Authentication Bypass by Capture-replay vulnerability exists that could cause execution of unauthorized Modbus functions on the controller when hijacking an authenticated Modbus session. Affected Products: EcoStruxure™ Control Expert (All Versions), EcoStruxure™ Process Expert (Versions prior to V2020), Modicon M340 CPU - part numbers BMXP34* (All Versions), Modicon M580 CPU - part numbers BMEP* and BMEH* (All Versions), Modicon M580 CPU Safety - part numbers BMEP58*S and BMEH58*S (All Versions) | |||||
CVE-2022-0222 | 1 Schneider-electric | 28 Modicon M340 Bmxnoe0100, Modicon M340 Bmxnoe0100 Firmware, Modicon M340 Bmxnoe0110 and 25 more | 2022-11-30 | N/A | 7.5 HIGH |
A CWE-269: Improper Privilege Management vulnerability exists that could cause a denial of service of the Ethernet communication of the controller when sending a specific request over SNMP. Affected products: Modicon M340 CPUs(BMXP34* versions prior to V3.40), Modicon M340 X80 Ethernet Communication modules:BMXNOE0100 (H), BMXNOE0110 (H), BMXNOR0200H RTU(BMXNOE* all versions)(BMXNOR* versions prior to v1.7 IR24) | |||||
CVE-2022-37300 | 1 Schneider-electric | 70 Ecostruxure Control Expert, Ecostruxure Process Expert, Modicon M340 Bmxp341000 and 67 more | 2022-09-15 | N/A | 9.8 CRITICAL |
A CWE-640: Weak Password Recovery Mechanism for Forgotten Password vulnerability exists that could cause unauthorized access in read and write mode to the controller when communicating over Modbus. Affected Products: EcoStruxure Control Expert Including all Unity Pro versions (former name of EcoStruxure Control Expert) (V15.0 SP1 and prior), EcoStruxure Process Expert, Including all versions of EcoStruxure Hybrid DCS (former name of EcoStruxure Process Expert) (V2021 and prior), Modicon M340 CPU (part numbers BMXP34*) (V3.40 and prior), Modicon M580 CPU (part numbers BMEP* and BMEH*) (V3.20 and prior). | |||||
CVE-2022-22724 | 1 Schneider-electric | 12 Modicon M340 Bmxp341000, Modicon M340 Bmxp341000 Firmware, Modicon M340 Bmxp342000 and 9 more | 2022-02-25 | 5.0 MEDIUM | 7.5 HIGH |
A CWE-400: Uncontrolled Resource Consumption vulnerability exists that could cause a denial of service on ports 80 (HTTP) and 502 (Modbus), when sending a large number of TCP RST or FIN packets to any open TCP port of the PLC. Affected Product: Modicon M340 CPUs: BMXP34 (All Versions) | |||||
CVE-2013-2763 | 1 Schneider-electric | 24 Modicon M340 Bmx Noc 0401, Modicon M340 Bmx Noc 0401 Firmware, Modicon M340 Bmx Noe 0100 and 21 more | 2022-01-31 | 5.0 MEDIUM | N/A |
** DISPUTED ** The Schneider Electric M340 PLC modules allow remote attackers to cause a denial of service (resource consumption) via unspecified vectors. NOTE: the vendor reportedly disputes this issue because it "could not be duplicated" and "an attacker could not remotely exploit this observed behavior to deny PLC control functions." | |||||
CVE-2019-6855 | 1 Schneider-electric | 44 Ecostruxure Control Expert, Modicon M340 Bmxp341000, Modicon M340 Bmxp341000 Firmware and 41 more | 2022-01-31 | 7.5 HIGH | 7.3 HIGH |
Incorrect Authorization vulnerability exists in EcoStruxure Control Expert (all versions prior to 14.1 Hot Fix), Unity Pro (all versions), Modicon M340 (all versions prior to V3.20) , and Modicon M580 (all versions prior to V3.10), which could cause a bypass of the authentication process between EcoStruxure Control Expert and the M340 and M580 controllers. | |||||
CVE-2021-22790 | 1 Schneider-electric | 49 Modicon M340 Bmxp341000, Modicon M340 Bmxp342010, Modicon M340 Bmxp342020 and 46 more | 2021-09-13 | 4.0 MEDIUM | 6.5 MEDIUM |
A CWE-125: Out-of-bounds Read vulnerability that could cause a Denial of Service on the Modicon PLC controller / simulator when updating the controller application with a specially crafted project file exists in Modicon M580 CPU (part numbers BMEP* and BMEH*, all versions), Modicon M340 CPU (part numbers BMXP34*, all versions), Modicon MC80 (part numbers BMKC80*, all versions), Modicon Momentum Ethernet CPU (part numbers 171CBU*, all versions), PLC Simulator for EcoStruxureª Control Expert, including all Unity Pro versions (former name of EcoStruxureª Control Expert, all versions), PLC Simulator for EcoStruxureª Process Expert including all HDCS versions (former name of EcoStruxureª Process Expert, all versions), Modicon Quantum CPU (part numbers 140CPU*, all versions), Modicon Premium CPU (part numbers TSXP5*, all versions). | |||||
CVE-2021-22791 | 1 Schneider-electric | 49 Modicon M340 Bmxp341000, Modicon M340 Bmxp342010, Modicon M340 Bmxp342020 and 46 more | 2021-09-13 | 4.0 MEDIUM | 6.5 MEDIUM |
A CWE-787: Out-of-bounds Write vulnerability that could cause a Denial of Service on the Modicon PLC controller / simulator when updating the controller application with a specially crafted project file exists in Modicon M580 CPU (part numbers BMEP* and BMEH*, all versions), Modicon M340 CPU (part numbers BMXP34*, all versions), Modicon MC80 (part numbers BMKC80*, all versions), Modicon Momentum Ethernet CPU (part numbers 171CBU*, all versions), PLC Simulator for EcoStruxureª Control Expert, including all Unity Pro versions (former name of EcoStruxureª Control Expert, all versions), PLC Simulator for EcoStruxureª Process Expert including all HDCS versions (former name of EcoStruxureª Process Expert, all versions), Modicon Quantum CPU (part numbers 140CPU*, all versions), Modicon Premium CPU (part numbers TSXP5*, all versions). | |||||
CVE-2021-22789 | 1 Schneider-electric | 49 Modicon M340 Bmxp341000, Modicon M340 Bmxp342010, Modicon M340 Bmxp342020 and 46 more | 2021-09-13 | 4.0 MEDIUM | 6.5 MEDIUM |
A CWE-119: Improper Restriction of Operations within the Bounds of a Memory Buffer vulnerability that could cause a Denial of Service on the Modicon PLC controller / simulator when updating the controller application with a specially crafted project file exists in Modicon M580 CPU (part numbers BMEP* and BMEH*, all versions), Modicon M340 CPU (part numbers BMXP34*, all versions), Modicon MC80 (part numbers BMKC80*, all versions), Modicon Momentum Ethernet CPU (part numbers 171CBU*, all versions), PLC Simulator for EcoStruxureª Control Expert, including all Unity Pro versions (former name of EcoStruxureª Control Expert, all versions), PLC Simulator for EcoStruxureª Process Expert including all HDCS versions (former name of EcoStruxureª Process Expert, all versions), Modicon Quantum CPU (part numbers 140CPU*, all versions), Modicon Premium CPU (part numbers TSXP5*, all versions). | |||||
CVE-2021-22792 | 1 Schneider-electric | 49 Modicon M340 Bmxp341000, Modicon M340 Bmxp342010, Modicon M340 Bmxp342020 and 46 more | 2021-09-13 | 5.0 MEDIUM | 7.5 HIGH |
A CWE-476: NULL Pointer Dereference vulnerability that could cause a Denial of Service on the Modicon PLC controller / simulator when updating the controller application with a specially crafted project file exists in Modicon M580 CPU (part numbers BMEP* and BMEH*, all versions), Modicon M340 CPU (part numbers BMXP34*, all versions), Modicon MC80 (part numbers BMKC80*, all versions), Modicon Momentum Ethernet CPU (part numbers 171CBU*, all versions), PLC Simulator for EcoStruxureª Control Expert, including all Unity Pro versions (former name of EcoStruxureª Control Expert, all versions), PLC Simulator for EcoStruxureª Process Expert including all HDCS versions (former name of EcoStruxureª Process Expert, all versions), Modicon Quantum CPU (part numbers 140CPU*, all versions), Modicon Premium CPU (part numbers TSXP5*, all versions). | |||||
CVE-2021-22779 | 1 Schneider-electric | 61 Ecostruxure Control Expert, Ecostruxure Process Expert, Modicon M340 Bmxp341000 and 58 more | 2021-07-26 | 6.4 MEDIUM | 9.1 CRITICAL |
Authentication Bypass by Spoofing vulnerability exists in EcoStruxure Control Expert (all versions prior to V15.0 SP1, including all versions of Unity Pro), EcoStruxure Control Expert V15.0 SP1, EcoStruxure Process Expert (all versions, including all versions of EcoStruxure Hybrid DCS), SCADAPack RemoteConnect for x70 (all versions), Modicon M580 CPU (all versions - part numbers BMEP* and BMEH*), Modicon M340 CPU (all versions - part numbers BMXP34*), that could cause unauthorized access in read and write mode to the controller by spoofing the Modbus communication between the engineering software and the controller. |