Filtered by vendor Schneider-electric
Subscribe
Filtered by product Interactive Graphical Scada System
Subscribe
Total
42 CVE
CVE | Vendors | Products | Updated | CVSS v2 | CVSS v3 |
---|---|---|---|---|---|
CVE-2022-32526 | 1 Schneider-electric | 1 Interactive Graphical Scada System | 2023-02-08 | N/A | 9.8 CRITICAL |
A CWE-120: Buffer Copy without Checking Size of Input vulnerability exists that could cause a stack-based buffer overflow, potentially leading to remote code execution when an attacker sends specially crafted setting value messages. Affected Products: IGSS Data Server - IGSSdataServer.exe (Versions prior to V15.0.0.22170) | |||||
CVE-2022-32522 | 1 Schneider-electric | 1 Interactive Graphical Scada System | 2023-02-08 | N/A | 9.8 CRITICAL |
A CWE-120: Buffer Copy without Checking Size of Input vulnerability exists that could cause a stack-based buffer overflow, potentially leading to remote code execution when an attacker sends specially crafted mathematically reduced data request messages. Affected Products: IGSS Data Server - IGSSdataServer.exe (Versions prior to V15.0.0.22170) | |||||
CVE-2022-32528 | 1 Schneider-electric | 1 Interactive Graphical Scada System | 2023-02-08 | N/A | 9.1 CRITICAL |
A CWE-306: Missing Authentication for Critical Function vulnerability exists that could cause access to manipulate and read files in the IGSS project report directory when an attacker sends specific messages. Affected Products: IGSS Data Server - IGSSdataServer.exe (Versions prior to V15.0.0.22170) | |||||
CVE-2022-32524 | 1 Schneider-electric | 1 Interactive Graphical Scada System | 2023-02-08 | N/A | 9.8 CRITICAL |
A CWE-120: Buffer Copy without Checking Size of Input vulnerability exists that could cause a stack-based buffer overflow, potentially leading to remote code execution when an attacker sends specially crafted time reduced data messages. Affected Products: IGSS Data Server - IGSSdataServer.exe (Versions prior to V15.0.0.22170) | |||||
CVE-2022-32525 | 1 Schneider-electric | 1 Interactive Graphical Scada System | 2023-02-08 | N/A | 9.8 CRITICAL |
A CWE-120: Buffer Copy without Checking Size of Input vulnerability exists that could cause a stack-based buffer overflow, potentially leading to remote code execution when an attacker sends specially crafted alarm data messages. Affected Products: IGSS Data Server - IGSSdataServer.exe (Versions prior to V15.0.0.22170) | |||||
CVE-2022-32529 | 1 Schneider-electric | 1 Interactive Graphical Scada System | 2023-02-08 | N/A | 9.8 CRITICAL |
A CWE-120: Buffer Copy without Checking Size of Input vulnerability exists that could cause a stack-based buffer overflow, potentially leading to remote code execution when an attacker sends specially crafted log data request messages. Affected Products: IGSS Data Server - IGSSdataServer.exe (Versions prior to V15.0.0.22170) | |||||
CVE-2022-32523 | 1 Schneider-electric | 1 Interactive Graphical Scada System | 2023-02-08 | N/A | 9.8 CRITICAL |
A CWE-120: Buffer Copy without Checking Size of Input vulnerability exists that could cause a stack-based buffer overflow, potentially leading to remote code execution when an attacker sends specially crafted online data request messages. Affected Products: IGSS Data Server - IGSSdataServer.exe (Versions prior to V15.0.0.22170) | |||||
CVE-2022-32527 | 1 Schneider-electric | 1 Interactive Graphical Scada System | 2023-02-08 | N/A | 9.8 CRITICAL |
A CWE-120: Buffer Copy without Checking Size of Input vulnerability exists that could cause a stack-based buffer overflow, potentially leading to remote code execution when an attacker sends specially crafted alarm cache data messages. Affected Products: IGSS Data Server - IGSSdataServer.exe (Versions prior to V15.0.0.22170) | |||||
CVE-2022-2329 | 1 Schneider-electric | 1 Interactive Graphical Scada System | 2023-02-08 | N/A | 9.8 CRITICAL |
A CWE-190: Integer Overflow or Wraparound vulnerability exists that could cause heap-based buffer overflow, leading to denial of service and potentially remote code execution when an attacker sends multiple specially crafted messages. Affected Products: IGSS Data Server - IGSSdataServer.exe (Versions prior to V15.0.0.22073) | |||||
CVE-2022-24324 | 1 Schneider-electric | 1 Interactive Graphical Scada System | 2023-02-08 | N/A | 9.8 CRITICAL |
A CWE-120: Buffer Copy without Checking Size of Input vulnerability exists that could cause a stack-based buffer overflow potentially leading to remote code execution when an attacker sends a specially crafted message. Affected Products: IGSS Data Server - IGSSdataServer.exe (Versions prior to V15.0.0.22073) | |||||
CVE-2019-6827 | 1 Schneider-electric | 1 Interactive Graphical Scada System | 2022-10-13 | 6.8 MEDIUM | 7.8 HIGH |
A CWE-787: Out-of-bounds Write vulnerability exists in Interactive Graphical SCADA System (IGSS), Version 14 and prior, which could cause a software crash when data in the mdb database is manipulated. | |||||
CVE-2020-7478 | 1 Schneider-electric | 1 Interactive Graphical Scada System | 2022-10-06 | 5.0 MEDIUM | 7.5 HIGH |
A CWE-22: Improper Limitation of a Pathname to a Restricted Directory exists in IGSS (Versions 14 and prior using the service: IGSSupdate), which could allow a remote unauthenticated attacker to read arbitrary files from the IGSS server PC on an unrestricted or shared network when the IGSS Update Service is enabled. | |||||
CVE-2020-7479 | 1 Schneider-electric | 1 Interactive Graphical Scada System | 2022-10-06 | 4.6 MEDIUM | 7.8 HIGH |
A CWE-306: Missing Authentication for Critical Function vulnerability exists in IGSS (Versions 14 and prior using the service: IGSSupdate), which could allow a local user to execute processes that otherwise require escalation privileges when sending local network commands to the IGSS Update Service. | |||||
CVE-2020-7552 | 1 Schneider-electric | 1 Interactive Graphical Scada System | 2022-01-01 | 6.8 MEDIUM | 7.8 HIGH |
A CWE-787: Out-of-bounds Write vulnerability exists in IGSS Definition (Def.exe) version 14.0.0.20247, that could cause Remote Code Execution when malicious CGF (Configuration Group File) file is imported to IGSS Definition. | |||||
CVE-2020-7551 | 1 Schneider-electric | 1 Interactive Graphical Scada System | 2022-01-01 | 6.8 MEDIUM | 7.8 HIGH |
A CWE-787: Out-of-bounds Write vulnerability exists in IGSS Definition (Def.exe) version 14.0.0.20247, that could cause Remote Code Execution when malicious CGF (Configuration Group File) file is imported to IGSS Definition. | |||||
CVE-2021-22762 | 1 Schneider-electric | 1 Interactive Graphical Scada System | 2021-06-15 | 6.8 MEDIUM | 7.8 HIGH |
A CWE-22: Improper Limitation of a Pathname to a Restricted Directory vulnerability exists inIGSS Definition (Def.exe) V15.0.0.21140 and prior that could result in remote code execution, when a malicious CGF or WSP file is being parsed by IGSS Definition. | |||||
CVE-2021-22761 | 1 Schneider-electric | 1 Interactive Graphical Scada System | 2021-06-15 | 6.8 MEDIUM | 7.8 HIGH |
A CWE-119: Improper Restriction of Operations within the Bounds of a Memory Buffer vulnerability exists inIGSS Definition (Def.exe) V15.0.0.21140 and prior that could result in disclosure of information or remote code e+F15xecution due to missing length check on user supplied data, when a malicious CGF file is imported to IGSS Definition. | |||||
CVE-2021-22760 | 1 Schneider-electric | 1 Interactive Graphical Scada System | 2021-06-15 | 6.8 MEDIUM | 7.8 HIGH |
A CWE-763: Release of invalid pointer or reference vulnerability exists inIGSS Definition (Def.exe) V15.0.0.21140 and prior that could result in loss of data or remote code execution due to missing checks of user-supplied input data, when a malicious CGF file is imported to IGSS Definition. | |||||
CVE-2021-22759 | 1 Schneider-electric | 1 Interactive Graphical Scada System | 2021-06-15 | 6.8 MEDIUM | 7.8 HIGH |
A CWE-416: Use after free vulnerability exists inIGSS Definition (Def.exe) V15.0.0.21140 and prior that could result in loss of data or remote code execution due to use of unchecked input data, when a malicious CGF file is imported to IGSS Definition. | |||||
CVE-2021-22754 | 1 Schneider-electric | 1 Interactive Graphical Scada System | 2021-06-15 | 6.8 MEDIUM | 7.8 HIGH |
A CWE-787: Out-of-bounds write vulnerability exists inIGSS Definition (Def.exe) V15.0.0.21140 and prior that could result in loss of data or remote code execution due to lack of proper validation of user-supplied data, when a malicious CGF file is imported to IGSS Definition. |