Vulnerabilities (CVE)

Join the Common Vulnerabilities and Exposures (CVE) community and start to get notified about new vulnerabilities.

Filtered by vendor Iconics Subscribe
Filtered by product Genesis32
Total 10 CVE
CVE Vendors Products Updated CVSS v2 CVSS v3
CVE-2020-12013 2 Iconics, Mitsubishielectric 11 Bizviz, Energy Analytix, Facility Analytix and 8 more 2021-11-04 6.4 MEDIUM 9.1 CRITICAL
A specially crafted WCF client that interfaces to the may allow the execution of certain arbitrary SQL commands remotely. This affects: Mitsubishi Electric MC Works64 Version 4.02C (10.95.208.31) and earlier, all versions; Mitsubishi Electric MC Works32 Version 3.00A (9.50.255.02); ICONICS GenBroker64, Platform Services, Workbench, FrameWorX Server v10.96 and prior; ICONICS GenBroker32 v9.5 and prior.
CVE-2020-12011 2 Iconics, Mitsubishielectric 11 Bizviz, Energy Analytix, Facility Analytix and 8 more 2020-07-29 7.5 HIGH 9.8 CRITICAL
A specially crafted communication packet sent to the affected systems could cause a denial-of-service condition or allow remote code execution. This issue affects: Mitsubishi Electric MC Works64 version 4.02C (10.95.208.31) and earlier, all versions; MC Works32 version 3.00A (9.50.255.02); ICONICS GenBroker64, Platform Services, Workbench, FrameWorX Server version 10.96 and prior; GenBroker32 version 9.5 and prior.
CVE-2020-12007 2 Iconics, Mitsubishielectric 11 Bizviz, Energy Analytix, Facility Analytix and 8 more 2020-07-29 7.5 HIGH 9.8 CRITICAL
A specially crafted communication packet sent to the affected devices could allow remote code execution and a denial-of-service condition due to a deserialization vulnerability. This issue affects: Mitsubishi Electric MC Works64 version 4.02C (10.95.208.31) and earlier, all versions; Mitsubishi Electric MC Works32 version 3.00A (9.50.255.02); ICONICS GenBroker64, Platform Services, Workbench, FrameWorX Server version 10.96 and prior; ICONICS GenBroker32 version 9.5 and prior.
CVE-2020-12009 2 Iconics, Mitsubishielectric 11 Bizviz, Energy Analytix, Facility Analytix and 8 more 2020-07-29 5.0 MEDIUM 7.5 HIGH
A specially crafted communication packet sent to the affected device could cause a denial-of-service condition due to a deserialization vulnerability. This affects: Mitsubishi Electric MC Works64 Version 4.02C (10.95.208.31) and earlier, all versions; Mitsubishi Electric MC Works32 Version 3.00A (9.50.255.02); ICONICS GenBroker64, Platform Services, Workbench, FrameWorX Server v10.96 and prior; ICONICS GenBroker32 v9.5 and prior.
CVE-2020-12015 2 Iconics, Mitsubishielectric 11 Bizviz, Energy Analytix, Facility Analytix and 8 more 2020-07-22 5.0 MEDIUM 7.5 HIGH
A specially crafted communication packet sent to the affected systems could cause a denial-of-service condition due to improper deserialization. This issue affects: Mitsubishi Electric MC Works64 version 4.02C (10.95.208.31) and earlier, all versions; Mitsubishi Electric MC Works32 version 3.00A (9.50.255.02); ICONICS GenBroker64, Platform Services, Workbench, FrameWorX Server version 10.96 and prior; ICONICS GenBroker32 version 9.5 and prior.
CVE-2011-5089 1 Iconics 2 Bizviz, Genesis32 2017-08-28 10.0 HIGH N/A
Buffer overflow in the Security Login ActiveX controls in ICONICS GENESIS32 8.05, 9.0, 9.1, and 9.2 and BizViz 8.05, 9.0, 9.1, and 9.2 allows remote attackers to cause a denial of service (application crash) or possibly execute arbitrary code via a long password.
CVE-2011-2089 1 Iconics 2 Bizviz, Genesis32 2017-08-28 9.3 HIGH N/A
Stack-based buffer overflow in the SetActiveXGUID method in the VersionInfo ActiveX control in GenVersion.dll 8.0.138.0 in the WebHMI subsystem in ICONICS BizViz 9.x before 9.22 and GENESIS32 9.x before 9.22 allows remote attackers to execute arbitrary code via a long string in the argument. NOTE: some of these details are obtained from third party information.
CVE-2014-0758 1 Iconics 1 Genesis32 2014-02-24 9.3 HIGH N/A
An ActiveX control in GenLaunch.htm in ICONICS GENESIS32 8.0, 8.02, 8.04, and 8.05 allows remote attackers to execute arbitrary programs via a crafted HTML document.
CVE-2012-3018 1 Iconics 2 Bizviz, Genesis32 2012-07-31 4.4 MEDIUM N/A
The lockout-recovery feature in the Security Configurator component in ICONICS GENESIS32 9.22 and earlier and BizViz 9.22 and earlier uses an improper encryption algorithm for generation of an authentication code, which allows local users to bypass intended access restrictions and obtain administrative access by predicting a challenge response.
CVE-2011-5088 1 Iconics 2 Bizviz, Genesis32 2012-04-18 9.3 HIGH N/A
The GENESIS32 IcoSetServer ActiveX control in ICONICS GENESIS32 9.21 and BizViz 9.21 configures the trusted zone on the basis of user input, which allows remote attackers to execute arbitrary code via a crafted web site, related to a "Workbench32/WebHMI component SetTrustedZone Policy vulnerability."