Total
17 CVE
CVE | Vendors | Products | Updated | CVSS v2 | CVSS v3 |
---|---|---|---|---|---|
CVE-2020-7533 | 1 Schneider-electric | 32 140cpu65260, 140cpu65260 Firmware, 140noc77101 and 29 more | 2022-04-25 | 7.5 HIGH | 9.8 CRITICAL |
A CWE-255: Credentials Management vulnerability exists in Web Server on Modicon M340, Modicon Quantum and ModiconPremium Legacy offers and their Communication Modules (see security notification for version information) which could cause the execution of commands on the webserver without authentication when sending specially crafted HTTP requests. | |||||
CVE-2020-7543 | 1 Schneider-electric | 32 Bmxp341000, Bmxp341000 Firmware, Bmxp342000 and 29 more | 2021-08-18 | 5.0 MEDIUM | 7.5 HIGH |
A CWE-754: Improper Check for Unusual or Exceptional Conditions vulnerability exists in Modicon M580, Modicon M340, Legacy Controllers Modicon Quantum & Modicon Premium (see security notifications for affected versions), that could cause denial of service when a specially crafted Read Physical Memory request over Modbus is sent to the controller. | |||||
CVE-2020-7537 | 1 Schneider-electric | 38 Bmxp341000, Bmxp341000 Firmware, Bmxp342000 and 35 more | 2021-08-18 | 5.0 MEDIUM | 7.5 HIGH |
A CWE-754: Improper Check for Unusual or Exceptional Conditions vulnerability exists in Modicon M580, Modicon M340, Legacy Controllers Modicon Quantum & Modicon Premium (see security notifications for affected versions), that could cause denial of service when a specially crafted Read Physical Memory request over Modbus is sent to the controller. | |||||
CVE-2020-7542 | 1 Schneider-electric | 40 140cpu65150, 140cpu65150 Firmware, Bmxp341000 and 37 more | 2021-08-18 | 5.0 MEDIUM | 7.5 HIGH |
A CWE-754: Improper Check for Unusual or Exceptional Conditions vulnerability exists in Modicon M580, Modicon M340, Legacy Controllers Modicon Quantum & Modicon Premium (see security notifications for affected versions), that could cause denial of service when a specially crafted Read Physical Memory request over Modbus is sent to the controller. | |||||
CVE-2020-7541 | 1 Schneider-electric | 40 140cpu65150, 140cpu65150 Firmware, 140noc77101 and 37 more | 2020-12-14 | 5.0 MEDIUM | 5.3 MEDIUM |
A CWE-425: Direct Request ('Forced Browsing') vulnerability exists in the Web Server on Modicon M340, Legacy Offers Modicon Quantum and Modicon Premium and associated Communication Modules (see security notification for affected versions), that could cause disclosure of sensitive data when sending a specially crafted request to the controller over HTTP. | |||||
CVE-2020-7540 | 1 Schneider-electric | 46 140cpu65150, 140cpu65150 Firmware, 140cpu65160 and 43 more | 2020-12-14 | 7.5 HIGH | 9.8 CRITICAL |
A CWE-306: Missing Authentication for Critical Function vulnerability exists in the Web Server on Modicon M340, Legacy Offers Modicon Quantum and Modicon Premium and associated Communication Modules (see security notification for affected versions), that could cause unauthenticated command execution in the controller when sending special HTTP requests. | |||||
CVE-2020-7539 | 1 Schneider-electric | 40 140cpu65150, 140cpu65150 Firmware, 140noc77101 and 37 more | 2020-12-14 | 5.0 MEDIUM | 7.5 HIGH |
A CWE-754 Improper Check for Unusual or Exceptional Conditions vulnerability exists in the Web Server on Modicon M340, Legacy Offers Modicon Quantum and Modicon Premium and associated Communication Modules (see security notification for affected versions), that could cause a denial of service vulnerability when a specially crafted packet is sent to the controller over HTTP. | |||||
CVE-2020-7536 | 1 Schneider-electric | 20 Bmxnoe0100, Bmxnoe0100 Firmware, Bmxnoe0110 and 17 more | 2020-12-14 | 7.8 HIGH | 7.5 HIGH |
A CWE-754:Improper Check for Unusual or Exceptional Conditions vulnerability exists in Modicon M340 CPUs (BMXP34* versions prior to V3.30) Modicon M340 Communication Ethernet modules (BMXNOE0100 (H) versions prior to V3.4 BMXNOE0110 (H) versions prior to V6.6 BMXNOR0200H all versions), that could cause the device to be unreachable when modifying network parameters over SNMP. | |||||
CVE-2020-7535 | 1 Schneider-electric | 42 140cpu65150, 140cpu65150 Firmware, 140cpu65160 and 39 more | 2020-12-14 | 5.0 MEDIUM | 7.5 HIGH |
A CWE-22: Improper Limitation of a Pathname to a Restricted Directory ('Path Traversal' Vulnerability Type) vulnerability exists in the Web Server on Modicon M340, Legacy Offers Modicon Quantum and Modicon Premium and associated Communication Modules (see security notification for affected versions), that could cause disclosure of information when sending a specially crafted request to the controller over HTTP. | |||||
CVE-2020-7549 | 1 Schneider-electric | 38 140cpu65150, 140cpu65150 Firmware, 140noc78000 and 35 more | 2020-12-14 | 5.0 MEDIUM | 5.3 MEDIUM |
A CWE-754: Improper Check for Unusual or Exceptional Conditions vulnerability exists in the Web Server on Modicon M340, Legacy Offers Modicon Quantum and Modicon Premium and associated Communication Modules (see security notification for affected versions), that could cause denial of HTTP and FTP services when a series of specially crafted requests is sent to the controller over HTTP. | |||||
CVE-2017-6017 | 1 Schneider-electric | 30 Bmxnoc0401, Bmxnoc0401 Firmware, Bmxnoe0100 and 27 more | 2018-12-24 | 7.8 HIGH | 7.5 HIGH |
A Resource Exhaustion issue was discovered in Schneider Electric Modicon M340 PLC BMXNOC0401, BMXNOE0100, BMXNOE0110, BMXNOE0110H, BMXNOR0200H, BMXP341000, BMXP342000, BMXP3420102, BMXP3420102CL, BMXP342020, BMXP342020H, BMXP342030, BMXP3420302, BMXP3420302H, and BMXP342030H. A remote attacker could send a specially crafted set of packets to the PLC causing it to freeze, requiring the operator to physically press the reset button on the PLC in order to recover. | |||||
CVE-2018-7241 | 1 Schneider-electric | 114 140cpu31110, 140cpu31110 Firmware, 140cpu31110c and 111 more | 2018-12-05 | 10.0 HIGH | 9.8 CRITICAL |
Hard coded accounts exist in Schneider Electric's Modicon Premium, Modicon Quantum, Modicon M340, and BMXNOR0200 controllers in all versions of the communication modules. | |||||
CVE-2018-7242 | 1 Schneider-electric | 114 140cpu31110, 140cpu31110 Firmware, 140cpu31110c and 111 more | 2018-12-05 | 5.0 MEDIUM | 9.8 CRITICAL |
Vulnerable hash algorithms exists in Schneider Electric's Modicon Premium, Modicon Quantum, Modicon M340, and BMXNOR0200 controllers in all versions of the communication modules. The algorithm used to encrypt the password is vulnerable to hash collision attacks. | |||||
CVE-2018-7762 | 1 Schneider-electric | 114 140cpu31110, 140cpu31110 Firmware, 140cpu31110c and 111 more | 2018-05-24 | 5.0 MEDIUM | 7.5 HIGH |
A vulnerability exists in the web services to process SOAP requests in Schneider Electric's Modicon M340, Modicon Premium, Modicon Quantum PLC, BMXNOR0200 which could allow result in a buffer overflow. | |||||
CVE-2018-7761 | 1 Schneider-electric | 114 140cpu31110, 140cpu31110 Firmware, 140cpu31110c and 111 more | 2018-05-24 | 7.5 HIGH | 9.8 CRITICAL |
A vulnerability exists in the HTTP request parser in Schneider Electric's Modicon M340, Modicon Premium, Modicon Quantum PLC, BMXNOR0200 which could allow arbitrary code execution. | |||||
CVE-2018-7760 | 1 Schneider-electric | 114 140cpu31110, 140cpu31110 Firmware, 140cpu31110c and 111 more | 2018-05-24 | 7.5 HIGH | 9.8 CRITICAL |
An authorization bypass vulnerability exists in Schneider Electric's Modicon M340, Modicon Premium, Modicon Quantum PLC, BMXNOR0200. Requests to CGI functions allow malicious users to bypass authorization. | |||||
CVE-2018-7759 | 1 Schneider-electric | 114 140cpu31110, 140cpu31110 Firmware, 140cpu31110c and 111 more | 2018-05-24 | 5.0 MEDIUM | 7.5 HIGH |
A buffer overflow vulnerability exists in Schneider Electric's Modicon M340, Modicon Premium, Modicon Quantum PLC, BMXNOR0200. The buffer overflow vulnerability is caused by the length of the source string specified (instead of the buffer size) as the number of bytes to be copied. |