CVE-2019-5172 1 Wago 2 Pfc200, Pfc200 Firmware 2020-03-17 7.2 HIGH 7.8 HIGH
An exploitable command injection vulnerability exists in the iocheckd service ‘I/O-Check’ function of the WAGO PFC 200 Firmware version 03.02.02(14). An attacker can send a specially crafted packet to trigger the parsing of this cache file. At 0x1e840 the extracted ntp value from the xml file is used as an argument to /etc/config-tools/config_sntp time-server-%d=<contents of ntp node> using sprintf(). This command is later executed via a call to system(). This is done in a loop and there is no limit to how many ntp entries will be parsed from the xml file.
CVE-2019-5158 1 Wago 1 E\!cockpit 2020-03-17 4.3 MEDIUM 7.8 HIGH
An exploitable firmware downgrade vulnerability exists in the firmware update package functionality of the WAGO e!COCKPIT automation software v1.6.1.5. A specially crafted firmware update file can allow an attacker to install an older firmware version while the user thinks a newer firmware version is being installed. An attacker can create a custom firmware update package with invalid metadata in order to trigger this vulnerability.
CVE-2019-5178 1 Wago 2 Pfc200, Pfc200 Firmware 2020-03-17 4.6 MEDIUM 7.8 HIGH
An exploitable stack buffer overflow vulnerability vulnerability exists in the iocheckd service ‘I/O-Check’ functionality of WAGO PFC 200 Firmware version 03.02.02(14). An attacker can send a specially crafted packet to trigger the parsing of this cache file. The destination buffer sp+0x440 is overflowed with the call to sprintf() for any hostname values that are greater than 1024-len(‘/etc/config-tools/change_hostname hostname=‘) in length. A hostname value of length 0x3fd will cause the service to crash.
CVE-2019-5180 1 Wago 2 Pfc200, Pfc200 Firmware 2020-03-17 4.6 MEDIUM 7.8 HIGH
An exploitable stack buffer overflow vulnerability vulnerability exists in the iocheckd service ‘I/O-Check’ functionality of WAGO PFC 200 Firmware version 03.02.02(14). An attacker can send a specially crafted packet to trigger the parsing of this cache file. The destination buffer sp+0x440 is overflowed with the call to sprintf() for any ip values that are greater than 1024-len(‘/etc/config-tools/config_interfaces interface=X1 state=enabled ip-address=‘) in length. A ip value of length 0x3da will cause the service to crash.
CVE-2019-5179 1 Wago 2 Pfc200, Pfc200 Firmware 2020-03-17 4.6 MEDIUM 7.8 HIGH
An exploitable stack buffer overflow vulnerability vulnerability exists in the iocheckd service ‘I/O-Check’ functionality of WAGO PFC 200 Firmware version 03.02.02(14). An attacker can send a specially crafted packet to trigger the parsing of this cache file.
CVE-2019-5181 1 Wago 2 Pfc200, Pfc200 Firmware 2020-03-17 4.6 MEDIUM 7.8 HIGH
An exploitable stack buffer overflow vulnerability vulnerability exists in the iocheckd service ‘I/O-Check’ functionality of WAGO PFC 200 Firmware version 03.02.02(14). A specially crafted XML cache file written to a specific location on the device can cause a stack buffer overflow, resulting in code execution. An attacker can send a specially crafted packet to trigger the parsing of this cache file. The destination buffer sp+0x440 is overflowed with the call to sprintf() for any subnetmask values that are greater than 1024-len(‘/etc/config-tools/config_interfaces interface=X1 state=enabled subnet-mask=‘) in length. A subnetmask value of length 0x3d9 will cause the service to crash.
CVE-2019-5168 1 Wago 2 Pfc200, Pfc200 Firmware 2020-03-16 7.2 HIGH 7.8 HIGH
An exploitable command injection vulnerability exists in the iocheckd service ‘I/O-Check’ function of the WAGO PFC 200 version 03.02.02(14). An attacker can send a specially crafted XML cache file At 0x1e8a8 the extracted domainname value from the xml file is used as an argument to /etc/config-tools/edit_dns_server domain-name=<contents of domainname node> using sprintf().This command is later executed via a call to system().
CVE-2019-5161 1 Wago 2 Pfc200, Pfc200 Firmware 2020-03-13 9.0 HIGH 9.1 CRITICAL
An exploitable remote code execution vulnerability exists in the Cloud Connectivity functionality of WAGO PFC200 versions 03.02.02(14), 03.01.07(13), and 03.00.39(12). A specially crafted XML file will direct the Cloud Connectivity service to download and execute a shell script with root privileges.
CVE-2019-5107 1 Wago 1 E\!cockpit 2020-03-13 5.0 MEDIUM 7.5 HIGH
A cleartext transmission vulnerability exists in the network communication functionality of WAGO e!Cockpit version 1.5.1.1. An attacker with access to network traffic can easily intercept, interpret, and manipulate data coming from, or destined for e!Cockpit. This includes passwords, configurations, and binaries being transferred to endpoints.
CVE-2019-5149 1 Wago 4 Pfc100, Pfc100 Firmware, Pfc200 and 1 more 2020-03-13 5.0 MEDIUM 7.5 HIGH
The WBM web application on firmwares prior to 03.02.02 and 03.01.07 on the WAGO PFC100 and PFC2000, respectively, runs on a lighttpd web server and makes use of the FastCGI module, which is intended to provide high performance for all Internet applications without the penalties of Web server APIs. However, the default configuration of this module appears to limit the number of concurrent php-cgi processes to two, which can be abused to cause a denial of service of the entire web server. This affects WAGO PFC200 Firmware version 03.00.39(12) and version 03.01.07(13), and WAGO PFC100 Firmware version 03.00.39(12) and version 03.02.02(14).
CVE-2019-5177 1 Wago 2 Pfc200, Pfc200 Firmware 2020-03-12 2.1 LOW 5.5 MEDIUM
An exploitable stack buffer overflow vulnerability vulnerability exists in the iocheckd service ‘I/O-Check’ functionality of WAGO PFC 200 Firmware version 03.02.02(14). The destination buffer sp+0x440 is overflowed with the call to sprintf() for any domainname values that are greater than 1024-len(‘/etc/config-tools/edit_dns_server domain-name=‘) in length. A domainname value of length 0x3fa will cause the service to crash.
CVE-2019-5077 1 Wago 4 Pfc 100, Pfc 100 Firmware, Pfc 200 and 1 more 2020-02-10 8.5 HIGH 9.1 CRITICAL
An exploitable denial-of-service vulnerability exists in the iocheckd service ‘’I/O-Chec’’ functionality of WAGO PFC 200 Firmware versions 03.01.07(13) and 03.00.39(12), and WAGO PFC 100 Firmware version 03.00.39(12). A specially crafted set of packets can cause a denial of service, resulting in the device entering an error state where it ceases all network communications. An attacker can send unauthenticated packets to trigger this vulnerability.
CVE-2019-5082 1 Wago 4 Pfc100, Pfc100 Firmware, Pfc200 and 1 more 2020-01-22 7.5 HIGH 9.8 CRITICAL
An exploitable heap buffer overflow vulnerability exists in the iocheckd service I/O-Check functionality of WAGO PFC200 Firmware version 03.01.07(13), WAGO PFC200 Firmware version 03.00.39(12), and WAGO PFC100 Firmware version 03.00.39(12). A specially crafted set of packets can cause a heap buffer overflow, potentially resulting in code execution. An attacker can send unauthenticated packets to trigger this vulnerability.
CVE-2019-5073 1 Wago 4 Pfc 100, Pfc 100 Firmware, Pfc 200 and 1 more 2019-12-27 5.0 MEDIUM 5.3 MEDIUM
An exploitable information exposure vulnerability exists in the iocheckd service "I/O-Check" functionality of WAGO PFC200 Firmware versions 03.01.07(13) and 03.00.39(12), and WAGO PFC100 Firmware version 03.00.39(12). A specially crafted set of packets can cause an external tool to fail, resulting in uninitialized stack data to be copied to the response packet buffer. An attacker can send unauthenticated packets to trigger this vulnerability.
CVE-2019-5078 1 Wago 4 Pfc 100, Pfc 100 Firmware, Pfc 200 and 1 more 2019-12-27 9.4 HIGH 9.1 CRITICAL
An exploitable denial of service vulnerability exists in the iocheckd service "I/O-Check" functionality of WAGO PFC200 Firmware versions 03.01.07(13) and 03.00.39(12), and WAGO PFC100 Firmware version 03.00.39(12). A specially crafted set of packets can cause a denial of service, resulting in the device entering an error state where it ceases all network communications. An attacker can send unauthenticated packets to trigger this vulnerability.
CVE-2019-5079 1 Wago 4 Pfc 100, Pfc 100 Firmware, Pfc 200 and 1 more 2019-12-27 7.5 HIGH 9.8 CRITICAL
An exploitable heap buffer overflow vulnerability exists in the iocheckd service "I/O-Check" functionality of WAGO PFC200 Firmware versions 03.01.07(13) and 03.00.39(12), and WAGO PFC100 Firmware version 03.00.39(12). A specially crafted set of packets can cause a heap buffer overflow, potentially resulting in code execution. An attacker can send unauthenticated packets to trigger this vulnerability.
CVE-2019-5080 1 Wago 4 Pfc 100, Pfc 100 Firmware, Pfc 200 and 1 more 2019-12-27 6.4 MEDIUM 9.1 CRITICAL
An exploitable denial-of-service vulnerability exists in the iocheckd service "I/O-Check" functionality of WAGO PFC 200 Firmware versions 03.01.07(13) and 03.00.39(12), and WAGO PFC100 Firmware version 03.00.39(12). A single packet can cause a denial of service and weaken credentials resulting in the default documented credentials being applied to the device. An attacker can send an unauthenticated packet to trigger this vulnerability.
CVE-2018-8836 1 Wago 16 750-829, 750-829 Firmware, 750-831 and 13 more 2019-10-09 5.0 MEDIUM 5.3 MEDIUM
Wago 750 Series PLCs with firmware version 10 and prior include a remote attack may take advantage of an improper implementation of the 3 way handshake during a TCP connection affecting the communications with commission and service tools. Specially crafted packets may also be sent to Port 2455/TCP/IP, used in Codesys management software, which may result in a denial-of-service condition of communications with commissioning and service tools.
CVE-2018-5459 1 Wago 19 750-8202, 750-8202\/025-000, 750-8202\/025-001 and 16 more 2019-10-09 7.5 HIGH 9.8 CRITICAL
An Improper Authentication issue was discovered in WAGO PFC200 Series 3S CoDeSys Runtime versions 2.3.X and 2.4.X. An attacker can execute different unauthenticated remote operations because of the CoDeSys Runtime application, which is available via network by default on Port 2455. An attacker could execute some unauthenticated commands such as reading, writing, or deleting arbitrary files, or manipulate the PLC application during runtime by sending specially-crafted TCP packets to Port 2455.
CVE-2019-12549 1 Wago 6 852-1305, 852-1305 Firmware, 852-1505 and 3 more 2019-06-19 10.0 HIGH 9.8 CRITICAL
WAGO 852-303 before FW06, 852-1305 before FW06, and 852-1505 before FW03 devices contain hardcoded private keys for the SSH daemon. The fingerprint of the SSH host key from the corresponding SSH daemon matches the embedded private key.