The Emerson ROC and FloBoss RTU product lines through 2022-05-02 perform insecure filesystem operations. They utilize the ROC protocol (4000/TCP, 5000/TCP) for communications between a master terminal and RTUs. Opcode 203 of this protocol allows a master terminal to transfer files to and from the flash filesystem and carrying out arbitrary file and directory read, write, and delete operations.
References
Link | Resource |
---|---|
https://www.cisa.gov/uscert/ics/advisories/icsa-22-223-04 | Mitigation Third Party Advisory US Government Resource |
https://www.forescout.com/blog/ | Third Party Advisory |
Configurations
Configuration 1 (hide)
AND |
|
Configuration 2 (hide)
AND |
|
Configuration 3 (hide)
AND |
|
Configuration 4 (hide)
AND |
|
Configuration 5 (hide)
AND |
|
Information
Published : 2022-08-16 06:15
Updated : 2022-08-17 12:35
NVD link : CVE-2022-30264
Mitre link : CVE-2022-30264
JSON object : View
CWE
CWE-345
Insufficient Verification of Data Authenticity
Products Affected
emerson
- roc827
- roc800l_firmware
- roc827_firmware
- dl8000_firmware
- fb3000_rtu
- fb3000_rtu_firmware
- roc809_firmware
- roc800l
- roc809
- dl8000