Show plain JSON{"cve": {"data_type": "CVE", "references": {"reference_data": [{"url": "https://search.abb.com/library/Download.aspx?DocumentID=8DBD000063&LanguageCode=en&DocumentPartId=&Action=Launch", "name": "https://search.abb.com/library/Download.aspx?DocumentID=8DBD000063&LanguageCode=en&DocumentPartId=&Action=Launch", "tags": ["Vendor Advisory"], "refsource": "CONFIRM"}]}, "data_format": "MITRE", "description": {"description_data": [{"lang": "en", "value": "Improper Input Validation vulnerability in the APDU parser in the Bidirectional Communication Interface (BCI) IEC 60870-5-104 function of Hitachi Energy RTU500 series allows an attacker to cause the receiving RTU500 CMU of which the BCI is enabled to reboot when receiving a specially crafted message. By default, BCI IEC 60870-5-104 function is disabled (not configured). This issue affects: Hitachi Energy RTU500 series CMU Firmware version 12.0.* (all versions); CMU Firmware version 12.2.* (all versions); CMU Firmware version 12.4.* (all versions)."}]}, "problemtype": {"problemtype_data": [{"description": [{"lang": "en", "value": "CWE-20"}]}]}, "data_version": "4.0", "CVE_data_meta": {"ID": "CVE-2021-35533", "ASSIGNER": "cybersecurity@hitachienergy.com"}}, "impact": {"baseMetricV2": {"cvssV2": {"version": "2.0", "baseScore": 7.1, "accessVector": "NETWORK", "vectorString": "AV:N/AC:M/Au:N/C:N/I:N/A:C", "authentication": "NONE", "integrityImpact": "NONE", "accessComplexity": "MEDIUM", "availabilityImpact": "COMPLETE", "confidentialityImpact": "NONE"}, "severity": "HIGH", "acInsufInfo": false, "impactScore": 6.9, "obtainAllPrivilege": false, "exploitabilityScore": 8.6, "obtainUserPrivilege": false, "obtainOtherPrivilege": false, "userInteractionRequired": false}, "baseMetricV3": {"cvssV3": {"scope": "UNCHANGED", "version": "3.1", "baseScore": 7.5, "attackVector": "NETWORK", "baseSeverity": "HIGH", "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H", "integrityImpact": "NONE", "userInteraction": "NONE", "attackComplexity": "LOW", "availabilityImpact": "HIGH", "privilegesRequired": "NONE", "confidentialityImpact": "NONE"}, "impactScore": 3.6, "exploitabilityScore": 3.9}}, "publishedDate": "2021-11-26T17:15Z", "configurations": {"nodes": [{"children": [{"children": [], "operator": "OR", "cpe_match": [{"cpe23Uri": "cpe:2.3:o:abb:rtu500_firmware:12.0:*:*:*:*:*:*:*", "cpe_name": [], "vulnerable": true}, {"cpe23Uri": "cpe:2.3:o:abb:rtu500_firmware:12.2:*:*:*:*:*:*:*", "cpe_name": [], "vulnerable": true}, {"cpe23Uri": "cpe:2.3:o:abb:rtu500_firmware:12.4:*:*:*:*:*:*:*", "cpe_name": [], "vulnerable": true}]}, {"children": [], "operator": "OR", "cpe_match": [{"cpe23Uri": "cpe:2.3:h:abb:rtu500:-:*:*:*:*:*:*:*", "cpe_name": [], "vulnerable": false}]}], "operator": "AND", "cpe_match": []}], "CVE_data_version": "4.0"}, "lastModifiedDate": "2021-11-30T19:24Z"}